Warning, Heating element installation – Steffes 8188 User Manual

Page 17

Advertising
background image

Step 3 Install element lead insulators. These ceramic

insulators MUST maintain lead wire spacings as
shown in Figure 15.

Step 4 Lower the insulation blankets back into position, one at a time. Carefully

tuck the sides of the insulation into the edges, corners, and around the
exposed portions of the heating element to ensure maximum efficiency.

Step 5 Reinstall the galvanized front panel and secure it to the system using the

screws originally removed.

Step 6 Route element harnesses through connectors, using one connector/harness until tape is centered in

connector. If installing two Storage Modules, use left hand bank of relays for left hand and right hand for
right hand. One harness per module is shorter and must be used for inside element connections.

Step 7 Attach element lead wires to element terminals. Start at the top using the appropriate color chart below.

Repeat pattern as necessary.

277/347V = Black (Top)

208/240V = Black (Top)

240V = Black (Top)

Systems

White

3phase

Red

1phase

Red

Red

Systems

Blue

Systems

Black

White

Black

Red

Blue

Red

White

Blue

Installation

FIGURE 15

FIGURE 14

Š

ŠŠ

Š

Š HAZARDOUS VOLTAGE: Risk of electric

shock, injury, or death.

Š

ŠŠ

Š

Š DO NOT remove the electrical panel

cover while system is energized.

Š

ŠŠ

Š

Š Elements MUST be positioned prop-

erly to avoid short circuiting against
any surfaces within the system.

Š

ŠŠ

Š

Š Risk of improper operation or equipment

damage. On Dual Storage Module
systems, it is critical to route the correct
harness to each of the Storage Modules.
Mis-routing of harness will result in
improper operation and equipment
damage. Make certain the harness
connected to the right side relay bank in
the electrical panel is routed to the right
side Storage Module.

WARNING

HEATING ELEMENT INSTALLATION

Step 1 After all bricks are loaded and rigid insulation boards

are in place, insert the heating elements through the
insulation, sliding them in until the cement side rails
are flush with the front side of the ceramic brick.

Make sure the elements designated as
Air Handler side elements are installed
on the Air Handler side of the Storage
Module(s).

Step 2 Route the element termination head

with ceramic insulator to the appro-
priate side of the Storage Module(s).
Insert the lead into position as
shown in Figure 14.

Element leads must never
cross each other.

T

HERM

E

LECT

I

NSTALLATION

„

3.08