Caution, Brick core temperature sensor installation, Core temperature sensor connections figure 16 – Steffes 8188 User Manual

Page 18

Advertising
background image

I

NSTALLATION

„

3.09

T

HERM

E

LECT

Installation

Step 3 Insert the brick core temperature sensors through the holes in the galvanized front panel. The sensors

must pass through the blanket and board insulation and into the brick core. Use the sensors to aid in
making a passageway by rotating the sensors while gently pushing inward.

Step 4 Once brick core sensors are installed, re-install sensor mounting screws to secure and ground the sensors.

Step 5 Re-install the painted front panel, using previously removed screws.

BRICK CORE TEMPERATURE SENSOR INSTALLATION

Step 1 Remove the screw(s) by the brick core temperature sensor connector

holes in the galvanized front panel.

Step 2 Route the brick core temperature sensors through the clear plastic

tube until within six inches of the relay driver board. Cut tube and
sensor wires to length as needed. The yellow wire from each sensor
must be connected to the Y terminal of the proper sensor connection
terminal block, and red to R. Polarity of sensors is critical.

Sensor connections MUST be installed as follows:

Single Module - 8150 or 8180 (Figure 16)

• Bottom sensor to core C

• Second sensor to core D

• Third (if equipped) to core E

Dual Module - 8155, 8185, and 8188 (Figure 16)

• Left module

• Right module

• Bottom sensor to core F

• Bottom sensor to core C

• Second sensor to core G

• Second sensor to core D

• Third (if equipped) to core H

• Third (if equipped) to core E

Risk of improper operation.
Proper installation of the brick
core temperature sensor is
critical to the operation of the
heating system. Read and
follow installation instructions
carefully.

CAUTION

CORE TEMPERATURE SENSOR CONNECTIONS

FIGURE 16

Models: 8150 & 8180

Models: 8155 & 8188

In systems using both an 80kW and 53kW Storage Module, the 53kW Storage Module must be
installed on the left side of the Air Handler.

Connect To Core "H"

80 Kw Module Only

Connect To

Core "C"

Connect To

Core "D"

Core

Temperature

Sensors

Connect To Core "E"

80 Kw Module Only

Core

Temperature

Sensors

Connect To

Core "F"

Connect To

Core "G"

Relay

Driver

Board

Connect To Core "E"

80 Kw Module Only

Core

Temperature

Sensors

Connect To

Core "D"

Connect To

Core "C"

Relay

Driver

Board