10

To reduce the risk of SEVERE INJURY or DEATH:
• ANY maintenance to the operator or in the area near the

operator MUST NOT be performed until disconnecting the
electrical power and locking-out the power via the operator
power switch. Upon completion of maintenance the area
MUST be cleared and secured, at that time the unit may be
returned to service.

• Disconnect power at the fuse box BEFORE proceeding.

Operator MUST be properly grounded and connected in
accordance with local electrical codes. The operator should
be on a separate fused line of adequate capacity.

• ALL electrical connections MUST be made by a qualified

individual.

• DO NOT install ANY wiring or attempt to run the operator

without consulting the wiring diagram. We recommend that
you install an optional reversing edge BEFORE proceeding
with the control station installation.

• ALL power wiring should be on a dedicated circuit and well

protected. The location of the power disconnect should be
visible and clearly labeled.

• ALL power and control wiring MUST be run in separate

conduit.

P O W E R W I R I N G & G R O U N D W I R I N G

ATTENTION

AVERTISSEMENT

AVERTISSEMENT

AVERTISSEMENT

WARNING

CAUTION

WARNING

WARNING

WARNING

PRECAUCIÓN

ADVERTENCIA

ADVERTENCIA

ADVERTENCIA

POWER WIRING CONNECTIONS

1. Connect power wires coming from the main to the captive

terminal block in the electrical box enclosure marked with the
label. All power and control wiring must be run in separate
conduit in accordance with local electrical codes.

2. Be sure to run all power wires through the conduit hole in the

electrical box enclosure marked with the label shown below.

NOTE: Must use #14 AWG or thicker wire for power wiring.

ON THREE PHASE MACHINES ONLY: Incorrect phasing of the
power supply will cause the motor to rotate in the wrong
direction. To change motor rotation, exchange incoming power
leads L1 and L2.

GROUND WIRING CONNECTIONS

1. Connect earth ground to the chassis ground screw in the

electrical box enclosure.

2. Use same conduit entry into the electrical box as the power

wiring.

IMPORTANT NOTE: This unit must be properly grounded. Failure
to properly ground this unit could result in electric shock and
serious injury.

Single Phase Power Wiring

Line Power

115/230 Vac

Single Phase

Gnd

Neutral

Hot

Line Power

208/230/380/460/575 Vac

Three Phase

Phase 3

Phase 2

Phase 1

Gnd

Three Phase Power Wiring