STEP 3

-

LOCATE THERMOSTAT

1.

Thermostat must be installed in same room as heater.

2.

Locate thermostat on an inside wall approximately 5 feet {153 cm} above the floor and at least 6 feet

{183 cm}from the heater.

3.

Do not locate thermostat so as to be effected by heat from sources other than the heater (i.e. direct

sunlight, lamps, T.V. sets, radiators, registers, etc.).

4.

Do not locate thermostat in unusually cool locations (i.e. outside wall, on a wall separating the heated

area from an unheated area, in drafts from stairwells, doors, windows, etc.).

5.

Install thermostat where there is good air circulation and where it is readily accessible for wiring, service
and adjustment. Never install in a corner, alcove, over or behind furniture or behind a door.

STEP 4

-

GAS SUPPLY ROUGH-IN

1.

An inch and a half (1-1/2”) opening is provided toward the right front of the liner bottom for installation

of the gas supply line. This opening facilitates installation of a gas supply line located inside the room

where the heater is installed. If the gas supply line is located in a stud space or other concealed area

consult the gas supplier, local code officials or the latest edition of ANSI Z223.1/NFPA 54 for special

instructions and approval for a concealed gas supply line. NOTE: If gas supply line is concealed, it must

be brought into the room under the heater as there must be a manual shut-off valve installed in the

gas supply line that is accessible from inside the room where the heater is installed.

2.

The valve must be connected only by means of a pipe union of the ground joint type.

3.

Mr. Installer, support gas valve, with a second wrench, when connecting the gas supply line, to prevent

damage.

4.

Install at least 3/8” gas supply line. Contact local gas supplier if any questions.

5.

Install a drip leg in gas supply line immediately upstream from the gas connection to heater. (see local

codes), and provide a 1/8” N.P.T. plugged tapping, accessible for test gauge connection and an indi-

vidual manual shut off valve accessible within room where heater is installed. (See Figure 4). The heater

and its individual shut off valve must be disconnected from the gas supply piping system during any

pressure testing of that system at test pressures in excess of 1/2 psig (3.5Pa). The heater must be

isolated from the gas supply piping system by closing its individual manual shut off valve during any

pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5Pa).

6.

Test all connections for leaks using a soapy solution. NEVER USE AN OPEN FLAME TO TEST

FOR LEAKS.

7.

The maximum inlet gas supply pressure for natural or L.P./Propane gas is 1/2 p.s.i. or 14” w.c.

8.

The minimum inlet gas supply pressure for the purpose of adjustment is 4.5” w.c. for natural gas or

11.0” w.c. for L.P./Propane gas.

FIGURE 4

WOW Heater

Outside Wall

Outside Wall

WOW Heater

Floor

Floor

Floor

Gas Supply

Gas Supply

Drip

Leg

Drip

Leg

Drip

Leg

Gas Supply

Manual shut off valve must

be in room with heater

Manual shut off

valve must be in

room with heater

Manual shut

off valve must

be in room with

heater

GAS SUPPLY FROM

CRAWL SPACE

GAS SUPPLY THROUGH

OUTSIDE WALL

GAS SUPPLY

INSIDE ROOM

WITH HEATER

WOW Heater

NOTE: 1/8” NPT plugged tapping must be provided in gas

supply line immediately ahead of the heater. This tapping may

be in the manual cutoff valve or in a separate fitting.