6 | electrical connection – GEA Bock HGZ7 User Manual

Page 25

Advertising
background image

D
GB
F
E

25

09726-11.2014-DGbF

6| Electrical connection

Terminal box

Fig. 30

6.5 Connection of the trigger unit MP10

Temperature monitoring connections:

Motor winding:

Terminals 1 - 2

Thermal protection thermostat:

Terminals 3 - 4

Restart prevention:

Terminals 5 - 6

ATTENTION
Terminals 1 - 6 on the trigger
unit MP 10 and terminals PTC
1 and PTC 2 on the compressor
terminal board must not come
into contact with mains voltage.
This would destroy the trigger
unit and PTC sensors.
The supply voltage at L1-N
(+/- for DC 24 V version) must
be identical to the voltage at
terminals 11, 12, 14 and 43.

INFO

The unit has a restart prevention device. After you have rectified the
fault, interrupt the mains voltage. This unlocks the restart prevention
device and the LEDs H1 and H2 go out.

INFO

Connect the trigger unit MP10 in accordance with the circuit
diagram. Protect the trigger unit with a delayed-action fuse (F) of
max. 4 A. In order to guarantee the protection function, install the
trigger unit as the first element in the control power circuit.

6.4 Electronic trigger unit MP10
The compressor motor is fitted with cold conductor temperature sensors (PTC) connected to the
electronic trigger unit MP 10 in the terminal box. Readiness to operate is signalled by the H3 LED
(green) after the power supply is applied. In the case of excess temperature in the motor winding, the
unit switches off the compressor and the H1 LED lights red.
The hot gas side of the compressor can also be protected against overtemperature using a thermal
protection thermostat (accessory). The H2 LED (red) is provided for the protection function.
The unit trips when an overload or inadmissible operating conditions occur. Find and remedy
the cause.