3 | areas of application – GEA Bock HGZ7 User Manual

Page 9

Advertising
background image

D
GB
F
E

9

09726-11.2014-DGbF

3| Areas of application

The compressors are filled at the factory with the following oil type:

- für R404A/R507, R410A

FUCHS Reniso Triton SE 55

- für R22

FUCHS Reniso SP 46

Compressors with ester oil charge (FUCHS Reniso Triton SE 55) are marked with an

X in the type

designation (e.g. HGZ

X7/2110-4 R404A).

3.1 Refrigerants
• HFKW :

R404A/R507, R410A

• (H)FCKW:

R22

3.2 Oil charge

INFO

For refilling, we recommend the above oil types.
Alternatives: see lubricants table, Chapter 8.5.

ATTENTION Compressor operation is possible within the operating limits

shown in the diagrams. Please note the significance
of the shaded areas. Thresholds should not be selected as design
or continuous operation points.

- Permissible ambient temperature (-20°C) - (+60°C)
- Max. permissible discharge end temperature 140 °C
- Max. permissible switching frequency 12x /h.
-

A minimum running time of 3 min. steady-state condition
(continuous operation) must be achieved.

For operation with supplementary cooling:
- Use only oils with high thermal stability.
- Avoid continuous operation near the threshold.

When operating in the vacuum range, there is a danger of air

entering on the suction side. This can cause chemical reactions,
a pressure rise in the condenser and an elevated compressed-gas
temperature. Prevent the ingress of air at all costs!

3.3 Limits of application

ATTENTION The correct oil level is shown

in figure 6.
Damage to the compressor
is possible if overfilled or
underfilled!

max.

min.

2,3 Ltr.

oil level

Fig. 6

~

~

Advertising