4 message communication 3-38, Com m uni ca tin g w ith fd -m h se ries – KEYENCE DL-EP1 User Manual

Page 66

Advertising
background image

- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (FD-MH) -

3-4 Message Communication

3-38

3

C

om
m

uni

ca

tin

g

w

ith FD

-M

H

Se
ries

Group2

0343H

(835)

Temperature

upper limit

setting value

*8

Indicates the temperature upper limit setting

value.

Parameter range:

0.1 to 99.9: Upper limit value (initial value: 80.0)

100.0: Upper limit detection invalid

R/W

DINT

0344H

(836)

Temperature

lower limit

setting value

*9

Indicates the temperature lower limit setting

value.

Parameter range:

0.1 to 99.9: Lower limit value (initial value: 5.0)

0.0: Lower limit detection invalid

R/W

DINT

0345H

(837)

Integrated

flow rate

setting value

1

Indicates the integrated flow rate setting value

1.

The value obtained by multiplying this value by

the value set in integrated flow rate units serves

as the actual integrated flow rate setting value.

Parameter range: 0 to 9999 (initial value: 150)

R/W

DINT

0346H

(838)

Integrated

flow rate

setting value

2

Indicates the integrated flow rate setting value

2.

The value obtained by multiplying this value by

the value set in integrated flow rate units serves

as the actual integrated flow rate setting value.

Parameter range: 0 to 9999 (initial value: 9999)

R/W

DINT

0347H

(839)

Instantaneous

flow rate

setting value

3 (P3)

*7

Indicates the instantaneous flow rate setting

value 3 (P3).

Parameter range:

FD-MH10A: 0.00 to 30.00 (initial value: 13.00)

FD-MH50A: 0.0 to 100.0 (initial value: 65.0)

FD-MH100A: 0.0 to 200.0 (initial value: 130.0)

FD-MH500A: 0.0 to 999.9 (initial value: 400.0)

R/W

DINT

0348H

(840)

Instantaneous

flow rate

setting value

4 (P4)

*7

Indicates the instantaneous flow rate setting

value 4 (P4).

Parameter range:

FD-MH10A: 0.00 to 30.00 (initial value: 20.00)

FD-MH50A: 0.0 to 100.0 (initial value: 100.0)

FD-MH100A: 0.0 to 200.0 (initial value: 200.0)

FD-MH500A: 0.0 to 999.9 (initial value: 500.0)

R/W

DINT

0349H

(841) to

035FH

(863)

(Reserved for system)

Group3

0360H

(864)

Group3 Entry

count

Indicates the group 3 entry count.

Parameter range: 5

R

DINT

0361H

(865)

Key lock

function

Indicates the key lock function.

Parameter range: 0 to 1

0: Key unlock (initial value)

1: Key lock

R/W

DINT

0362H

(866)

(Reserved for system)

0363H

(867)

Analog output

selection

*10

Indicates the analog output selection.

Parameter range: 0 to 1

0: Standard (initial value)

1: Free range analog

R/W

DINT

Class

Attribute

ID

Name

Description

Attribute

Data

Type