Data Processing Time

This section describes the length of time that lasts from detection by a sensor to data

processing by PLC.

Maximum data processing time = (1) + (2) + (3) + (4)

(1)PLC scan time

(2)RPI (Transmission cycle)

(3)DL-EP1 data communication time

(4)Sensor amplifier response time

(2)RPI is set with the scanner unit. It can be set in 0.5 ms increments between 0.5 ms

and 10000 ms.

(3)DL-EP1 data communication time

The time required for sending outputs and current value data from a sensor

amplifier to the DL-EP1 is as follows:

For details on the PLC scan time in (1) and the sensor amplifier response time in (4),

refer to the manual of each unit.

Number of connected sensor

amplifiers

Output, judgment value, or

current value

1

7.8 ms

2

9.8 ms

3

13.8 ms

4

15.8 ms

5

19.8 ms

6

21.8 ms

7

25.8 ms

8

27.8 ms

9

31.8 ms

10

33.8 ms

CPU unit

EtherNet/IP

scanner

DL-EP1

Sensor amplifier

(1)

(2)

(3)

(4)