3.0 INSTALLATION

3.1 Inspection On Arrival

1. Inspect the shipping crate for shipping damage before removing the

dust collector from the crate.


2. Report any damage to the delivery carrier. Whenever possible note on

bill of lading before trucker leaves.

3. Photograph the shipment before and during unpacking to document

damage.

4. Request a written inspection report from the claims inspector to

substantiate claim.

5. Report incomplete shipments to the delivery carrier and your AAF

representative.

6. Remove the upper crating material from the base skid. Remove lag

screws, strapping, etc., that attach the equipment to the skid.

3.2 Site Selection and Unit Location

1. The preferred and sometimes required location for a dust collector is

outdoors if there is a potential for fire or explosion.


2. The

Cyclone should be located with consideration for maintenance,

inspection, shortest possible run for duct and electrical work and
access for emptying dust receptacle (drum, bin or hopper).


3. When hazardous conditions or materials are present, consult with local

authorities for the proper location of the collector.

4. If unit is installed indoors and has an explosion vent, then provision

must be made to duct the explosion vent to outside of building, away
from normally occupied areas.

5. Prepare the concrete pad in the selected location. Anchor bolts should

be a minimum of 5/8” diameter, with 5” embedment. The pad design
and anchor bolt system should be calculated by a structural engineer.




- 3 -