CHAPTER 3 – INSTALLATION

OMM-0100_0B

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 51 of 156

GF-146

Ph.: 800-526-0288

PRI - 07/14/14

Figure 3-19: Condensate Box Draining

The condensate drainage system is designed to empty all the condensate produced by one
boiler only. Each boiler must be equipped with its own condensate drainage system or the
drainage system may malfunction

A condensate removal pump is required if the boiler is below the drain. When installing a
condensate pump, select one approved for use with condensing boilers and furnaces. The

pump should have an overflow switch to prevent property damage from condensate spillage.

3.13.1 Commonwealth of Massachusetts Special Requirement

When the boiler is installed and used in the Commonwealth of Massachusetts, a neutralization
unit MUST be installed in the condensate removal system.