AM Series Boilers and Water Heaters

CHAPTER 3 – INSTALLATION

Page 86 of 156

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0100_0B

PRI - 07/14/14

Ph.: 800-526-0288

GF-146

Gas Rating Conversion of Master Burner 1 (Cont.)

16. Check for any gas leaks on nut “H” as per Figure 3-42.

17. Turn the power ON to the unit.

18. Turn completely counter-clockwise screw “E” in Figure 3-45.

19. Check the gas supply pressure per Section 4.6. The minimum gas supply pressure must not

be less than 3” W.C. (7.6 mbar) and the maximum gas supply pressure must not be higher
than 13” W.C. (33 mbar).

20. Verify the

CO

2

rate and its adjustment per Section 4.7.

Figure 3-42: Dismantling the Gas Valve Figure 3-43: Lifting up the Gas valve

Figure 3-44: Gas Valve Orifice Figure 3-45: Gas Valve Adjustments