1 gas supply specifications, 2 manual gas shutoff valve, 3 external gas supply regulator – AERCO BMK 1.5 LN October 2012 User Manual

Page 19: Gf-120, Benchmark 1.5ln low nox boiler

Advertising
background image



CHAPTER 2

INSTALLATION

PR1: 10/18//12 AERCO International Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288 Page 19 of 166


GF-120

OMM-0041 0E

Benchmark 1.5LN Low NOx Boiler

Installation, Operation and Maintenance Manual

2.7.1

Gas Supply Specifications.

The gas supply input specifications to the unit for Natural Gas are as follows:

• The maximum static pressure to the unit must not exceed 14” W.C.
• The gas supply pressure to the unit must be of sufficient capacity to provide 1500 cfh

while maintaining the gas pressure at 4.0 inches W.C. for FM, or 4.2 inches W.C. for IRI
gas trains.

2.7.2

Manual Gas Shutoff Valve

A manual shut-off valve must be installed in the gas supply line upstream of the Boiler as shown
in Figure 2-6. Maximum allowable gas pressure to the Boiler is 14” W.C.

NOTE

Paragraph 2.7.3 applies only to bolier installations within the
Commonwealth of Massachusetts.

2.7.3

External Gas Supply Regulator

For Massachusetts installations, a mandatory external gas supply regulator must be positioned
as shown in Figure 2-6. The gas supply regulator must be properly vented to outdoors. Consult
the local gas utility for detailed requirements concerning venting of the the supply gas regulator.

NOTE

The external regulator must be capable of regulating 1,500,000
BTU/HR of natural gas while maintaining a gas pressure of 4.0”
W.C. to the boiler.

CAUTION

A lock-up style regulator MUST be used when gas supply
pressure will exceed 14” W.C.