CHAPTER 4
INITIAL START-UP

Page 54 of 166 AERCO International Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288 PR1:10/18/12

Benchmark 1.5LN Low NOx Boiler

Installation, Operation and Maintenance Manual

GF-120

OMM-0041 0E

Press the down ▼ arrow key until CAL Voltage 60% is displayed.

29.

Press the CHANGE key. CAL Voltage 60% will begin to flash.

30.

The oxygen level at the 60% valve position should be as shown below. Also, ensure that

31.

the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values
shown.

Table 4-3: Combustion Oxygen Levels for a

60% Air/Fuel Valve Position

Oxygen

%

± 0.2

Carbon

Monoxide

NOx

6.3 %

<50 ppm

<30 ppm

If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼

32.

arrow keys. This will adjust the output voltage to the blower motor as indicated on the

display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow
key decreases the oxygen level.

Once the oxygen level is within the specified range at 60%, press the ENTER key to

33.

store the selected blower output voltage for the 60% valve position.

Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.

34.

Press the CHANGE key. SET Valve Position will begin to flash.

35.

Press the ▼ arrow key until the SET Valve Position reads 45%, then press the ENTER

36.

key.

Press the ▼ arrow key until CAL Voltage 45% is displayed.

37.

Press the CHANGE key. CAL Voltage 45% will begin to flash.

38.

The oxygen level at the 45% valve position should be as shown below. Also, ensure that

39.

the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values
shown.

Table 4-4: Combustion Oxygen Levels for a

45% Air/Fuel Valve Position

Oxygen

%

± 0.2

Carbon

Monoxide

NOx

7.0 %

<50 ppm

<30 ppm

If the oxygen level is not wit

hin the specified range, adjust the level using the ▲ and ▼

40.

arrow keys. This will adjust the output voltage to the blower motor as indicated on the

display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow
key decreases the oxygen level.

Once the oxygen level is within the specified range at 45%, press the ENTER key to

41.

store the selected blower output voltage for the 45% valve position.

Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.

42.

Press the CHANGE key. SET Valve Position will begin to flash.

43.

Press the ▼ arrow key until the SET Valve Position reads 30%, then press the ENTER

44.

key.

Press the ▼ arrow key until CAL Voltage 30% is displayed.

45.

Press the CHANGE key. CAL Voltage 30% will begin to flash.

46.