5 setup menu, Gf-120, Benchmark 1.5ln low nox boiler – AERCO BMK 1.5 LN October 2012 User Manual

Page 37

Advertising
background image


CHAPTER 3

OPERATION

PR1: 10/18//12 AERCO International Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288 Page 37 of 166


GF-120

OMM-0041 0E

Benchmark 1.5LN Low NOx Boiler

Installation, Operation and Maintenance Manual

NOTE

The Outdoor Temp display item shown with an asterisk in Table 3-2 will not
be displayed unless the Outdoor Sensor function has been enabled in the
Configuration Menu (Table 3-4).

Table 3-2: Operating Menu

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

Status Message

Active Setpoint

40°F

240°F

AIR Temp

-70°F

245°F

Outdoor Temp*

-70°F

130°F

Valve Position In

0%

100% Valve Position

Flame Strength

0%

100%

Run Cycles

0

999,999,999

Run Hours

0

999,999,999

Fault Log

0

19

0

3.5 SETUP MENU

The Setup Menu (Table 3-3) permits the operator to enter the unit password (159) which is
required to change the menu options. To prevent unauthorized use, the password will time-out
after 1 hour. Therefore, the correct password must be reentered when required. In addition to
permitting password entries, the Setup Menu is also used to enter date and time, units of
temperature measurements and entries required for external communication and control of the
unit via the RS-232 port. A view-only software version display is also provided to indicate the
current Control Box software version.