APPENDIX A: MENU ITEM DESCRIPTIONS

Page

112 of 162 PR2: 05/09/12

Benchmark 1.5LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0C

GF-121

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Table A-1: Boiler Menu Item Descriptions

MENU LEVEL & OPTION

DESCRIPTION

TUNING MENU

Prop Band

Generates a fire rate based on the error that exists

between the setpoint temperature and the actual

outlet temperature. If the actual error is less than

the proportional band setting (1 to 120°F), the fire

rate will be less than 100%. If the error is equal to

or greater than the proportional band setting, the fire

rate will be 100%.

Integral Gain

This sets the fraction of the output, due to setpoint

error, to add or subtract from the output each minute

to move towards the setpoint. Gain is adjustable

from 0.00 to 1.00 (Default is 0.10).

Derivative Time

This value (0.0 to 20.0 min.) responds to the rate of

change of the setpoint error. This is the time that

this action advances the output.

Reset Defaults?

Allows Tuning Menu options to be reset to their

Factory Default values.