CHAPTER 4: INITIAL START-UP

PR2: 05/09/12 Page

49 of 162

Benchmark 1.5LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0C

GF-121

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

17. If necessary, adjust the iris air damper shown in Figure 4-5 until the oxygen level is

within the range specified in Table 4-1.

18. Once the oxygen level is within the specified range at 100%, lower the valve

position to 80%.

Figure 4-6: Iris Air Damper Location/Adjustment


NOTE

The remaining combustion calibration steps are performed

using the Combustion Cal Menu included in the C-More

Control System. The combustion calibration control functions

will be used to adjust the oxygen level (%) at air/fuel valve

positions of 80%, 60%, 45%, 30% and 16% as described in

the following steps. These steps assume that the inlet air

temperature is within the range of 50°F to 100°F.

19. Press the

MENU key on the front panel of the C-MORE and access the Setup

menu. Enter password

6817 and then press the ENTER key.

20. Press the

MENU key on the front panel of the C-MORE until Combustion Cal Menu

appears on the C-More display.

21. Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.
22. Press the

CHANGE key. SET Valve Position will begin to flash.

23. Press the ▲ arrow key until the SET Valve Position reads 80%. Press the

ENTER

key.

24. Next, press the down (▼) arrow key until CAL Voltage 80% is displayed.
25. Press the

CHANGE key and observe that CAL Voltage 80% is flashing.

26. The oxygen level at the 80% valve position should be as shown below. Also, ensure

that the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed

the values shown.