CHAPTER 2: INSTALLATION

Page

16 of 162 PR2: 05/09/12

Benchmark 1.5LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0C

GF-121

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Figure 2-5: Condensate Trap Installation: Older (left) and Newer (right) Style

2.7 GAS SUPPLY PIPING

The AERCO Benchmark 1.5 Gas Components and Supply Design Guide, GF-4030 must be

consulted prior to designing or installing any gas supply piping.

WARNING

NEVER USE MATCHES, CANDLES, FLAMES OR OTHER

SOURCES OF IGNITION TO CHECK FOR GAS LEAKS.

CAUTION

Many soaps used for gas pipe leak testing are corrosive to metals.

There-fore, piping must be rinsed thoroughly with clean water after

leak checks have been completed.

NOTE

All gas piping must be arranged so that it does not

interfere with removal of any covers, inhibit

service/maintenance, or restrict access between the unit

and walls, or another unit.

Benchmark 1.5 Dual-Fuel units contain two 1-1/2 inch gas inlet connections on the rear of the

unit as shown in Figure 2-3. If one of the fuel sources is not being piped due to its unavailability,

the inlet must be capped.
Prior to installation, all pipes should be de-burred and internally cleared of any scale, metal

chips or other foreign particles. Do Not install any flexible connectors or unapproved gas

fittings. Piping must be supported from the floor, ceiling or walls only and must not be supported

by the unit.
A suitable piping compound, approved for use with natural gas, should be used. Any excess

must be wiped off to prevent clogging of components.
To avoid unit damage when pressure testing gas piping, isolate the unit from the gas supply

piping. At no time should the gas pressure applied to the unit exceed 14” W.C. Leak test all

external piping thoroughly using a soap and water solution or suitable equivalent. The gas

piping used must meet all applicable codes.