C-More Controller for Benchmark, Innovation & KC

USER MANUAL

04/22/14

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913

Page 127 of 162

OMM-0032_0E

Phone: 800-526-0288

GF-112

Option 3 – Continued

Step 3 - Configure ALL C-More Units

On ALL Boilers:

1. Go to the Configuration Menu and set the BST Menu item to Enabled.

2. Go to the BST Menu and set the BST Mode item to BST Slave (for now).

On MASTER only:

3. Go to the BST Setpoint item and enter the Failsafe Setpoint.

4. Go to the BST Setup Menu item and set to Enabled.

5. Go to the BST Setpoint Mode item and select Outdoor Reset.

6. Go to the Head Temp Source item and select FFWD Temp.

7. Go to the BST Outdoor Sens item and select Enabled.

8. Go to the Outdoor Temp Source item and select Outdoor Temp.

When ALL C-More units have been configured:

9. Go to the BST Menu of the desired Master unit and set the BST Mode item to BST

MASTER.