C-More Controller for Benchmark, Innovation & KC

USER MANUAL

04/22/14

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913

Page 31 of 162

OMM-0032_0E

Phone: 800-526-0288

GF-112

Table 2-9: Diagnostics Menu

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

Exhaust Temp Sens

Enable, Disable

Disable

In Wtr Temp Sens

Enable, Disable

Disable

In Gas Press Sen

Enable, Disable

Disable

Gas Plate dp Sen

Enable, Disable

Disable

In Water Flw Sen

Enable, Disable

Disable

Display Test

Off, LEDs, 7-Seg Bar-graph

Off

Keypad Test

Off, Manual, Menu Up, Down, Change, Enter, Clear

(BACK Key exits test mode)

Off

Relay Test

(Allows user to force
outputs ON or OFF)

Off, Igniter ON/Igniter OFF, Blower ON/Blower OFF

Pump ON/Pump OFF, Aux ON/Aux OFF

Fault ON/Fault OFF

Off

Switch Test

(Allows user to view the
status of all switch
inputs)

Off, Exhaust sw ON/Exhaust sw OFF

SSOV sw ON/SSOV sw OFF

Blower Proof ON/Blower Proof OFF

Ignition sw ON/Ignition sw OFF

Over Temp sw ON/Over Temp sw OFF

Low Gas Pres ON/Low Gas Pres OFF

Hi Gas Pres ON/Hi Gas Pres OFF

Water Lev sw ON/Water Lev sw OFF

Rem Int sw ON/Rem Int sw OFF

Front Pnl sw ON/Front Pnl sw OFF

Delayed Int ON/Delayed Int OFF

Purge sw ON/Purge sw OFF

Off

Stepper Test

(Allows user to adjust
the stepper motor
position using the

and

▼ keys)

0%

100%

0%

Sensor Log Int

(Allows user to set the
time interval for logging
Sensor inputs in
Database)

Off

1 Min, 5 Min, 15 Min, 30 Min

1 Hr, 6 Hrs, 12 Hrs, or 24 Hrs

30 Min.