9.7 TROUBLESHOOTING

Faults which may occur during BST operation include the items listed below.

FAULT INDICATION

PROBABLE CAUSE

CORRECTIVE ACTION

OUTLET TEMPERATURE
display is flashing on 2 C-
More Control Panels

1. Two C-Mores have their

BST Mode menu option set
to BST Master

1. Check the BST Mode entries in the units

which have their displays flashing. Change
one of the BST Mode settings to BST Slave.

REMOTE LED on one or
more BST units is Off.

1. Improperly connected or

faulty RS485 Modbus
wiring.

2. Improper Comm address.



3. Unit Comm address is not

unique.

1. Check the polarity of the RS485 Comm

connections on the I/O board of the affected
unit. Also, ensure that all Modbus wiring
connections to the unit are secure.

2. Verify that the address of the affected unit is

within the allowable range (1 thru 8). The
address numbers do not have to be
sequential.

3. Check to ensure that none of the units have

the same Comm address.

Actuator-controlled
sequencing valve does not
open

1. Control cable not

connected to valve
actuator.

2. 24 VAC power not being

supplied to valve actuator.

3. Defective valve actuator.

1. Ensure that the control cable from the unit’s

I/O Box is connected to the valve actuator.

2. Remove the enclosure cover from the valve

actuator and verify that 24 VAC is present at
Terminal 2 of the actuator.

3. Replace valve actuator. Following

replacement, the actuator stroke will have to
be calibrated to ensure it fully opening and
closing.