Table 2-7: Sample Combustion Cal Menu (Version 3.08.xx)

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

CAL Voltage 16%

.25v

8.20v

1.90v

CAL Voltage 20%

.25v

8.20v

2.30v

CAL Voltage 30%

.25v

8.20v

2.80v

CAL Voltage 40%

.25v

8.20v

3.00v

CAL Voltage 50%

.25v

8.20v

3.60v

CAL Voltage 60%

.25v

8.20v

3.90

CAL Voltage 80%

.25v

8.20v

4.80

CAL Voltage 100%

.25v

8.20v

6.00v

SET Valve Position

0%

100%

0%

Blower Output

Monitor Blower Output

Voltage

.00

2.10 CALIBRATION MENU

The Calibration Menu is used by Factory Trained Service personnel to adjust or reset the
parameters listed in Table 2-8.

Table 2-8: Calibration Menu

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

Stepper Fbk

(Not adjustable via RS232
serial communication)

Cal 0%

Cal 100%

Verify 50%

Cal 0%

PWM In Adj

-5.0%

5.0%

0.0%

Supply Gas Pressure In Adj

-5.0%

5.0%

0.0%

Gas Plate dp In Adj

-5.0%

5.0%

0.0%

mA Out Adj

-1.0 mA

1.0 mA

0.0 mA

A/F Sensitivity

1%

5%

2%

Power Reset

Automatic orManual

Automatic

Water Temp Reset

Automatic or Manual

Automatic

Gas Press Reset

Automatic or Manual

Manual

Min Off Time

0 Min

15 Min

1 Min (Boiler)

0 Min (Water

Heater)

Heatr Tuning Dsp

(If Unit Type = Water Heater)

Enabled or Disabled

Disabled