Interconnecting Cables

Interconnecting cable conductor size is dependent upon
the distance between the control, switches, and potential
transformers. Maximum lengths of various cable combi-
nations for No. 18 through No. 12 AWG conductors are
shown in Table 2. The longest combination for the partic-
ular installation will determine the minimum conductor
size. All cables are to be the same conductor size.

Note:

If the control is equipped with the fault block accesso-
ry, see Table 3 for additional cable length limitations.

On the switch end, the cables are wired to connector
plugs provided as standard with the switches. On the S
control end, the cables are wired either directly to termi-
nal blocks in the control or to connector plugs provided
with the Plugs and Receptacles accessory. Figure 9
shows the location of the accessory plugs and recepta-
cles in the bottom of the control cabinet. See the appro-
priate switch installation manual for the location of the
plugs and receptacles on the switch.

Switch Cable

A conductor cable is required between the S control and
each high-voltage switch to operate the switches. This
cable is wired to a socket plug at the switch end and to
either a plug or TB1 at the control end. Pin identification,
and cable OD and maximum conductor size accommo-
dated by the plugs are shown in Figures 10 and 11.

Potential Transformer Cable

A four-conductor cable is required between the S control
and the potential transformers to transmit source voltage
intelligence and to supply operating power for the control.
This cable is wired to a five-pin socket plug or TB2 at the
control end. Pin socket identification, cable OD, and
maximum conductor size accommodated by the plugs
are shown in Figure 12.

Note:

Connectors are not supplied for the transformer end of
the cable.

S260-75-1

13

!

SAFETY

FOR LIFE

Maximum Length of

Cable Wire

Control Cable Combinations (ft.)

Size

VR, VLR, or VRV Switches

TSC Switch

(AWG)

A+B+D or C+B+D

A+B or A+D

or C+B or C+D

18

1450

1250

16

2300

2000

14

3700

3200

12

5900

5050

LOAD

S CONTROL

HV
SW
2

D

C

HV
SW
1

B

A

TABLE 2
Maximum Control Cable Lengths

Figure 9.
Plugs and receptacles accessory.

KEYWAY

PIN F

VIEW A-A

MAX. WIRE SIZE – NO.16 AWG

PIN INSERT CONNECTIONS INTO CONTROL

RUBBER GROMMET
ACCOMMODATES
1/2" TO 5/8" DIA. CABLE

A

A

KEYWAY

SOCKET E

MAX. WIRE SIZE – NO.12 AWG

SOCKET INSERT – CONNECTS INTO CONTROL

RUBBER GROMMET
ACCOMMODATES
3/8" TO 1/2" DIA. CABLE

A

A

Figure 10.
Switch cable plug for VR, VLR, VRV, and TSC.

Figure 12.
PT cable plug.

020079KM

Note: The control cable lengths are not applicable for the C

switch and the PST switch.

KEYWAY

PIN F


VIEW A-A

PIN INSERT CONNECTIONS INTO CONTROL

A

A

PST-6

8, 7, & 19 PIN RECEPTACLES

PST-9

8 & 19 PIN RECEPTACLES

A

F

E

G

D

C

B

A G

F

E

H

D

C

B

8 PIN 7 PIN 19 PIN

L M A

K U N B

C

D

P

V

T

J

R

S

E

F

H

G

Figure 11.
Switch cable plugs for PST-6 and PST-9.