Output of the Control

To determine if the problem is in the control or the high-
voltage transfer switch, proceed as follows:

1. Disconnect the switches from the control.

2. Place OPERATION SELECTOR switch (S3) to

MANUAL.

3. Place SOURCE PREFERENCE and RETURN

MODE switch (S4) to NO PREF.

4. With the control energized, check the voltage to

ground at the “Transfer Switch Operators” terminal
board, TB1, per Table 6.

5. If these output voltages are obtained, check the high-

voltage switch. If the output voltages are not
obtained, check the manual control functions.

High-Voltage Switch

Normal control output at TB1 but failure to operate sug-
gests a malfunctioning switch.

1. With an ohmmeter, check the resistance between

points of the high-voltage switch actuator per Table 5.

2. If the control circuit of the switch operator checks out,

the trouble may be mechanical. Refer to the mainte-
nance manual for the switch.

Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions

22

Switch

Ohmmeter Reading

Receptacle

Pin

Switch Open

Switch Closed

Type VR, VLR, VRV — Standard Operator

B to C

Motor

B to D

Trip Coil

B to E

0

D to F

0

0

Type VR, VLR, VRV — Quick Close Operator

A to D

*

B to C

Quick Close Coil

B to D

Trip Coil

B to E

0

D to F

0

0

Type TSC

B to C

Motor

B to F

Motor

B to E

0

D to F

0

Type PST-6 with C Interrupter #1

E to R

Close Coil

M to N

0

P to E

*

S to V

0

T to U

Trip Coil

Type PST-6 with C Interrupter #2

B to C

0

D to E

*

E to F

Close Coil

G to K

0

H to J

Trip Coil

Type PST-9 with C Interrupter #1

E to F

A to C

C to E

B to C

C to D

Type PST-9 with C Interrupter #2

L to M

0

G to J

0

J to L

Trip Coil

H to J

*

J to K

Close Coil

TABLE 5
Continuity Check of High-Voltage Switches

* Will read motor resistance if closing spring is not charged, will

read infinity if closing spring is charged.