Fault block shielded cable – Cooper Lighting S260-75-1 User Manual

Page 14

Advertising
background image

Fault Block Shielded Cable

Table 3 shows the maximum distance between the con-
trol and the high-voltage switches for a range of conduc-
tor sizes and fault-block settings. The table is based on
conductor voltage drop and saturation of the current
sensing transformers in the switch. Lower actuating lev-
els and lower multipliers could allow longer lines.
However, the limitation on switch control cable lengths,
Table 2, preclude their use.

Shielded cable is required between the transfer switches
and the S control for operating the fault block accessory.

The shield must be grounded to the equipment housing
at both the switch and control ends. Shield connections
are made at connector plug pin or socket as shown in
Figure 13. This pin mates with the receptacle pin or sock-
et which is grounded in the switch and in the control as
shown in Figures 6 and 8.

Type S Automatic Load-Transfer Control Installation, Operation, and Maintenance Instructions

14

TABLE 3
Fault Block Cable Limitations

Max. Distance in Feet

Phase

Between Switch and

Actuating

Con-

S Control

Current

ductor

Level

Size

For X 8

For X 6

For X 4

(Amps)

(AWG)

Multi-

Multi-

Multi-

plier

plier

plier

640

18

600

1000

1800

640

16

950

1600

2900

640

14

1500

2550

4600

640

12

2400

4000

7300

448

18

1100

1700

448

16

1800

2700

448

14

2800

4300

448

12

4500

6850

320

18

1800

320

16

2900

320

14

4600

320

12

7300

Figure 13.
Fault block cable plug.

KEYWAY

SOCKET A

SWITCH END

STRIP JACKET TO EXPOSE SHIELDING

RUBBER GROMMET
ACCOMMODATES
.50 TO .56 DIA. CABLE

A

A

KEYWAY

CONTROL END

PIN G

SOLDER #16 AWG JUMPER WIRE
FROM SHIELD TO PIN G TO
COMPLETE SHIELD CONNECTION

IMPORTANT: Only shielded cable is to be used on fault
block accessory and is mandatory to validate the
Cooper Power Systems warranty. Use of a non-shielded
cable could result in misoperation.

Advertising