All air from outdoors, Louvers and grilles – Kenmore 153.331492 User Manual

Page 17

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

gas utilization equipment in the area. If you are unsure that the
structure meets this requirement, contact your local gas utility
company or other qualified agency for a safety inspection.

Each of the two openings shall have a minimum free area of 1

square inch per 1,000 BTUH of the total input rating of all gas
utilization equipment in the confined area, but not less than 100
square inches (Figure 13).

FIGURE 13.

All Air from Outdoors

Outdoor fresh air can be provided to a confined area either
directly or by the use of vertical and horizontal ducts. The

fresh air can be taken from the outdoors or from crawl or attic
spaces that freely communicate with the outdoors. Attic or crawl
spaces cannot be closed and must be properly ventilated to the
outside.

Ductwork must be of the same cross-sectional area as the

free area of the opening to which they connect. The minimum
dimension of rectangular air ducts cannot be less than three

inches.

The size of each of the two openings is determined by the

method in which the air is to be provided. Refer to Table 3 to
calculate the minimum free area for each opening. Figures 14,
15, 16 and 17 are typical examples of each method.

Louvers and Grilles

In calculating free area for ventilation and combustion air supply

openings, consideration must be given to the blocking effect
of protection louvers, grilles, and screens. These devices can
reduce airflow, which in turn may require larger openings to
achieve the required minimum free area. Screens must not be
smaller than 1/4” mesh. If the free area through a particular
design of louver or grille is known, it should be used in
calculating the specified free area of the opening. If the design
and free area are not known, it can be assumed that most wood
louvers will allow 20 - 25% of free area while metal louvers and
grilles will allow 60 - 75% of free area.

Louvers and grilles must be locked open or interconnected with

the equipment so that they are opened automatically during
equipment operation.

Keep louvers and grilles clean and free of debris or other

obstructions.

TABLE 3

Minimum Free Area of Permanent Openings for Ventilation
and Combustion Air Supply - All Air from Outdoors Only.

Based on total BTUH input rating for all

within the confined space.

utilizing equipment

Opening Source

Minimum Free Area

Per Opening (sq. in.)

Reference

Drawing

‘Direct to outdoors

1 sq. in, per 4000 BTUH

Figure 14

Vertical Ducts

1 sq. in, per 4000 BTUH

Figure 15

Horizontal Ducts

1 sq. in, per 2000 BTUH

Figure 16

Single Opening

1 sq. in, per 3000 BTUH

Figure 17

Example: A water heater with an input rating of 50,000 BTUH using
horizontal ducts would require each opening to have a minimum free

area of 25 square inches.

Minimum free area = 50,000 BTUH x 1 sq. in. / 2000 BTUH = 25 sq.
in.

* These openings connect directly with the outdoors through a

ventilated attic, a ventilated crawl space, or through an outside
wall.

Consult the local codes of your area for specific ventilation and
combustion air requirements.

GABLE VENT

TO OUTDOORS

/

INSTALL ABOVE

INSULATION

^OUTLET

AIR TO

ATTIC 1 SO.

INCH PER

4000 BTUH

1 SO. INCH PER

4000 BTUH

OPEN

FOUNDATION-

VENT

ALL AIR FROM OUTDOORS; INLET AIR FROM VENTILATED

CRAWL SPACE/OUTLET AIR TO VENTILATED ATTIC

FIGURE 14.

ALL AIR FROM OUTDOORS THROUGH VENTILATED ATTIC

FIGURE 15.

17

Advertising
This manual is related to the following products: