Awarning, Installation instructions (cont’d), Venting (cont’d) – Kenmore POWER MISER 153.335816 User Manual

Page 16

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Advertising
background image

Installation Instructions (cont’d)

Venting (cont’d)

AWARNING

Be sure vent pipe is properly connected to prevent escape of
dangerous flue gases which could cause deadly asphyxiation.

VENTING

SYSTEM

EXAMPLE

INSTALLATIONS

FOR ALL MODELS

The vent piping

cannot

under any circumstances be run down^

hill.

AWARNING

Chemical vapor corrosion of the flue and vent system may

occur if air for combustion contains certain chemical vapors.
Spray can propellants, cleaning solvents, refrigerator and air
conditioner refrigerants, swimming pool chemicals, calcium

and sodium chloride, waxes, bleach, and process chemicals are

typical compounds which are potentially corrosive.

3" PVC SCHEDULE 40 VENT PIPING

Supplied in the carton with the water heater are;

1. A3' ABS Schedule 40-45° vent cap with wire screen.

2. A 3" PVC Schedule 40-90° street ell; used to connect the

vent pipe to the water heater when the vent pipe is to be
turned horizontally directly off the blower,

3- A 5' section of 3" PVC Schedule 40 pipe (more may be

required and must be supplied locally).

3" PVC SCHEDULE 40
90° ELBOW

r?

S’ SCHEDULE 40 PVC PIPE

0

^

VENT CAP

WITH SCREEN

1.

The water heater requires its own (separate) venting

system.

2. 3" PVC, ABS or CPVC Schedule 40 piping and fittings are

acceptable materials for the vent system on all 40 gallon
models and 50 gallon 40,000 BTU/HR models.

3.

It cannot be connected to existing vent piping or

chimney.

4. It must terminate horizontally to the outdoors.

The vent piping can be installed as follows:

1. No more than 3 elbows can be used.

16