Installation Instructions (cont’d)

Gas Piping

AWARNING

Make sure the gas supplied is the same type listed on the
model rating plate. The inlet gas pressure must not exceed

10.5 in. water column (2.6kPa) for natural gas or 13 in. water

column (3.2kPa) for propane (LR) gas. The minimum inlet
gas pressure listed on the model rating plate is for the pur­
pose of input adjustment.

AWARNING

If the gas control valve is subjected to pressures exceeding

'A

pound per square inch (3.5kPa), the damage to the gas con­
trol valve could result in a fire or explosion from leaking gas.

___

AWARNING

__

If the main gas line shutoff serving all gas appliances is used,
also turn "off” the gas at each appliance. Leave ail gas appli­
ances shut off until ^e water heater installation is complete.

AWARNING

Use pipe joint compound or teflon tape marked as being

resistant to the action of petroleum [Propane (L.P.)] gases.

SEDIMENT TRAP

A sediment trap shall be installed as close to the inlet of the
water heater as practical at the time of water heater installation.
The sediment trap shall be either a tee fitting with a capped nip­

ple in the bottom outlet or other device recognized as an effec­
tive sediment trap. If a tee fitting is used, it shall be installed in

conformance with one of the methods of installation shown
below.

Connecting the gas piping to the gas control valve of the water

heater can be accomplished by either of the two methods shown.

GAS PIPING WITH

FLEXIBLE CONNECTOR

A gas line of sufficient size must be run to the water heater.

Consult the latest edition of National Fuel Gas Code ANSI
Z223.1, also referred to as NFPA 54 and the gas company con­
cerning pipe size.

There must be:
• A readily accessible manual shut off valve in the gas supply line

serving the water heater, and

• A drip lee (sediment trap) ahead of the gas control valve to help

prevent dirt and foreign materials from entering the gas control
valve.

• A flexible gas connector or a ground joint union between the

shutoff valve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the

water heater. Use a soapy water solution, not a match or open

flame. Rinse off soapy solution and wipe dry.

Standard Models

are for installation up to 3,300 feet above sea

level.

High Altitude Models

are for installation from 3,300 to 5,500

feet above sea level.

If a standard model is installed above 3,300 feet or a high altitude
model is installed above 5,500 feet, the input rating must be
reduced at the rate of 4 percent for each 1,000 feet above sea level.
Contact your local Sears Service Center or gas utility for further
information.

AWARNING

The appliance and its gas connection must be leak tested

before placjpg the appliance in operation.

AWARNING

> The appliance and its individual shutoff valve must be discon­

nected fiwn the gas supply piping system during any pressure
testing of the gas system at test pressures in excess of 1/2

pound per square inch (3.5kPa).

• The appliance must be isolated from the gas supply piping sys­

tem by closing its individual manual shutoff v<ilw during any

pressure testing of the gas supply piping system at test pres­
sures equal or less than

\/l

pound per square inch (3.5kPa).

MANUAL SHUT OFF

VALVE

iq GAS SUPPLY PIPING

FLEXIBLE CAS CONNECTOR

LABELED AS COMPLYING

WITH ANSI

standards

GAS

CONTROL
VALVE

GAS PIPING WITH ALL BLACK IRON

PIPE TO GAS CONTROL

■ GAS SUPPLY PIPING

MANUAL SHUT OFF I

VALVE

GAS
CONTROL

valve

19

AWARNING

Contaminants in the gas lines may cause improper operation
of the gas control valve that may result in fire or explosion.

Before attaching the gas line be sure that all gas pipe is dean

on the inside. 1b trap any dirt or foreign material in the gas

supply line, a drip leg (sometimes called a sediment trap)
must be incorporated in the piping. The drip leg must be
readily accessible. Install in accordance with the “Gas Piping”
section. Refer to the latest edition of the National Fuel Gas
Code, ANSI Z223.1, also referred to as NFPA 54.