Installation Instructions (cont’d)

Combustion Air and Ventilation

for Appliances Located in

Unconfined Spaces

Unraiifiaed Space is a space whose volume is not less than 50
cubic feet per 1,000 Btu per hour of the aggregate input rating
of all appliances installed in that space. Rooms communicating
directly with the space in which the appliances are installei
through openings not furnished with doors, are considered a
part of the unconfined space

In unconfined spaces in buildings, infiltration may be adequate
to provide air for combustion, ventilation and dilution of flue
gases. However, in buildmgs of tight construction (for example,
weaker stripping, heavily insulated, caulked, vapor barrier, etc.),
additional^ air may need to be provided using the methods
described in Combustion Air and Ventilation for Appliances
Located in Confined Spaces, b.

Combustion Air and Ventilation

for Appliances Located in

Confined Spaces

^nfioed Space is a space whose volume is less than 50 cubic
feet per 1,000 Btu per hour of the aggregate input rating of all
appliances installed in that space,

a. ALL AIR FROM INSIDE BUILDINGS:

(See I^e 9 Figure 1, and F^ure 2 below)

The confined space shall be provided with two permanent
openings communicating direedy with an additional room(s)
of sufficient volume so that the combined volume of all
spaces meets the criteria for an unconfined space. The total
input of all ^ utilization equipment installed in the com­
bined space shall be considered in making this determination,

^ch openii^ shall have a minimum free area of one square
inch per 1,000 BT^ per hour of the total input raring of all

gas utilization equipment in the confined space, but not less

than 100 square inches. One opening shall commence within
12 inches of the top and one commencing within 12 inches

of the bottom of the enclosure.

CMMN6Y OH (MS VENT

~Flgur« 2

• ALL AIR FROM OUTDOORS:

(see Figures 3-5)

The confined space shall be provided with two permanent

openings, one commencing within 12 inches of the top and

one commencing within 12 inches from the bottom of the
enclosure. The openings shall communicate directly, or by
ducts, wiA the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors.

Figure 3

1. 'pCTien direaly communicating with the outdoors, each open­

ing shall have a minimum free area of 1 square inch per 4,000
BTU per hour of total input rating of all equipment in the

enclosure. (See Figure 3.)

2. When communicating with the outdoors through vertical

ducts, each opening shall have a minimum free area of 1
square inch per 4,000 BTU per hour of total input rating of
all equipment in the enclosure. (Sec Figure 4.)

Figure 4

3. When communicating with the outdoors through horizontal

ducts, each opening shall have a minimum fee area of 1

a

uare inch per 2,000 BTU per hour of total input rating of
equipment in the enclosure. (See Figure 5.)

Figure 5

Ol/aCTMACIUCT

NTT AM DUCT

10

4. When ducts arc used, they shall be of the same cross-sectional

area as the free area of the openings to which they connect.
The minimum short side dimension of rectangular air ducts
shall not be less than 3 inches. (See Figure 5.)

5. Louvers and Grilles: In calculatii^ free area, consideration

shall be given to the blocking effect of louvers, grilles or
screens protecting opening. Screens used shall not be smaller
than inch mesh. If the free area through a design of louver

or grille is known, it should be used in calculating the size
opening rec^ired to provide the free area specified. If the
design and free area is not known, it may be assumed that
wood louvers will be 20-25 percent fee area and metal louvers
and grilles will have 60-75 percent free area. Louvers and
grilles shall be fixed in the open position or interlocked with
the equipment so that they are opened automatically during
equipment operation.

6. Special Conditions Created by Mechanical Exhausting or

Fireplaces: Operation of exhaust fans, ventilation systems,
clothes dryets or fireplaces may create conditions requiring
special attention to avoid unsatisfretory operation of installed
gas utilization equipment.

'