Installation Instructions (cont’d)

Temperature-Pressure Relief Valve

AWARNING

At the time of manufacture this water heater was provided

with a combination temperature-pressures relief valve certified
by a nationally recognized testing laboratory that maintains
periodic inspection of production of listed equipment or mate­

rials, as meeting the requirements for Relief Valves and
Automatic Gas Shutoff Devices for Hot Water Supply Systems,
and the latest edition of ANSI Z21.22 and the code require­

ments of ASME. If replaced, the valve must meet the require­
ments of local codes, but not less than a combination tempera­
ture and pressure relief valve certified as meeting the require­
ments for Relief Valves and Automatic Gas Shutoff Devices for

Hot Water Supply Systems, ANSI Z2I.22 by a nationally recog­

nized testing laboratory that maintains periodic inspection of
production of listed equipment or materials.
The valve must be marlced with a maximum set pressure not

to exceed the marked hydrostatic working pressure of the
water heater (ISO tbsisq. in.) and a discharge capacity not less
than the water heater input rate as shown on the model rating

plate. (Electric beaters - watts divided by 1000 x 3415 equal
BTU/Hr. rate.)
Your local jurisdictional authority, while mandating the use of a

temperature-pressure relief valve complying with ANSI Z2I.22

and ASME, may require a valve model different from the one

furnished with the water heater.

Compliance with such local requirements must be satisfied by

the installer or end user of the water heater with a locally pre­

scribed temperature-pressure relief valve installed in the desig­
nated opening in the water heater in place of the foctory fur­

nished valve.
For safe operation of the water heater, the relief valve must not

be removed from it^ designated opening or plugged,
The temperature-pressure relief valve must be installed directly

into the fitting of the water heater designated for the relief valve.
Position the valve downward and provide tubing so that any dis­
charge will exit only within 6 inches above, or at any distance

below the structural floor. Be certain that no contact is made

with any live electrical part The discharge opening must not be

blocked or reduced in size under any circumstances. Excessive

length, over 10 feet, or use of more than four elbows can cause

restriction and reduce the discharge capacity of the valve.

No valve or other obstruction is to be placed between the relief

valve and the tank. Do not connect tubing directly to discharge

drain unless a 6" air gap is provided. To prevent bodily injury, haZ‘
ard to life, or property damage, the relief valve must be allowed
to discharge water in quantities should circumstances demand. If

the discharge pipe is not connected to a drain or other suitable
means, the water flow may cause property damage.
The Discharge Pipe:

• Must not be smaller in size than the outlet pipe size of the

valve, or have any reducing couplings or other restrictions.

• Must not be plugged or blocked.

• Must be of material listed for hot water distribution,
• Must be installed so as to allow complete drainage of both

the temperature-pressure relief valve, and the discharge

pipe.

• Must terminate at an adequate drain.

• Must not have any valve between the relief valve and tank.

AWARNING

The temperature-pressure relief valve must be manually

operated at least once a year. Caution should be taken to
ensure that (I) no one is in front of or around the outlet of
the temperature-pressure relief valve discharge line, and (2)
the water manually discharged will not cause any bodily

injury or property damage because the water may be

extremely hot.

If after manually operating the valve. It fells to completely
reset and continues to release water, immediately close the
cold water inlet to the water heater, follow the draining
instructions, and replace the temperature-pressure relief
valve with a new one.

COLD

TEM PERATURE-PRESSURE

RELIEF VALVE

DISCHARGE PIPE
(Do not cap or plug)

6" AIR GAP

RELIEF VALVE OPENING

Ac the cime of manufeiture, this water heater was provided with a combiraticm tem-
peracure>pressure relief valve listed as compFjnng with the standard

for

relief valves and

automatic gas shut<01! devices lor hot water suppiy systems, ANSI Z21.22. for safe
operation of the water heater, the relief vafve must not be removed from its designated

point of installation or plugged.
Your local jurisdictional authority, while mandating the use of a temperature-pressure

relief valve complying with ANSI

71

1.22 and ASMC may retjutre a valve model different

from the one furnished widi the water heater.
Compliance with such local requirements must be satisfied by the installer or end user
of the water heater with a locally prescribed temperature-pressure relief vafve installed

in the designated opening in the water heater.

See manual heading -“Temperature-Pressure Relief \^|ves” for installation and mainte­

nance of relief valve, discharge line, and ocher safety precautions.