10.6 Preset Point Output

Using this preset point output funciion, you can output a conlaci signal when the totalized

flow reaches its preset value. Proceed as follows to use this function.

Totalizer setting

Set necessary parameters and selections to use the totalizer. See 10,2, "Totalizer and

Pulse Outpul,”

Preset value setting

Set the desired preset value. See 8.2.1“Preset Count Value/’,

In case of the converter for special specifications (refer to 7.3.3 "Converter for

Special spccificaiions'% select the desired preset point output function.

8.2.20,'Trcset Function’’

DO/DI fundlun setting

Set DOl or D02 for use as a preset point output. Sec 8.2,9, "‘Digital I/O"

To dear (reset) the totalizer with an external signal, set DI as a Resei/Start signal.

In case of the converter for sjpecial specifications (refer to 7,3.3 "Converter for

Special specifications’’), select Digita! input Detective l.evel. 8.2.19 “DI detective

Lever’.

If you use the control keys on the panel (optional) to dear (reset) the totalizer, this

setting is not liecdud.

-