ANALOG 4mA and 20mA POINT ADJUSTMENT PARAMETERS


Each analog output is calibrated to 4mA and 20mA points, so each of the up to four analog
outputs has a 4mA and 20mA point setting – see the parameters below:

EI-1000

ANALOG OUTPUT 4.00 mA (ZERO) ADJUSTMENT: EI-1000

PARAMETER EI-1000: Ao.x

(x = 1,2,3, or 4)

Press


Set the left 4.00 mA analog output point using the up & down arrow pushbuttons. The display
will not show any indication that the left analog output is changing which is why one should
have a "mA" meter (i.e., DMM) connected to the appropriate output. The mA output range is
approximately 4.0 mA +/- 1.0 mA.

ANALOG OUTPUT 20.00 mA (SPAN) ADJUSTMENT: EI-1000

PARAMETER EI-1000: Ao.x

(x = 1,2,3, or 4)


Set the left 20.00 mA analog output point using the right up & down arrow pushbuttons. The
display will not show any indication that the left analog output is changing which is why one
should have a "mA" meter (i.e. DMM) connected to J3-1 & J3-2. The mA output range is
approximately 20.0 mA +/- 1.0 mA.

EI-2000

ANALOG OUTPUT 4.00 mA (ZERO) ADJUSTMENT: EI-2000

PARAMETER EI-2000: "AO x" " 4.00"

(x = 1,2,3, or 4)


Set the left 4.00 mA analog output point using the right up & down arrow pushbuttons. The
display will not show any indication that the left analog output is changing which is why one
should have a "mA" meter (i.e., DMM) connected to the appropriate output. The mA output
range is approximately 4.0 mA +/- 1.0 mA.

ANALOG OUTPUT 20.00 mA (SPAN) ADJUSTMENT: EI-2000

PARAMETER EI-2000: "AO x" "20.00"

(x = 1,2,3, or 4)


Set the left 20.00 mA analog output point using the right up & down arrow pushbuttons. The
display will not show any indication that the left analog output is changing which is why one
should have a "mA" meter (i.e. DMM) connected to J3-1 & J3-2. The mA output range is
approximately 20.0 mA +/- 1.0 mA.