POWER-UP FUNCTIONS

Power-up functions are activated by, first, powering down the meter, pressing the desired
pushbutton combination, and restoring power to the meter.


Restore all parameters and calibration to factory default settings.

This function erases all non-volatile memory and restores the instrument to a factory default
setup. The 4-20mA analog outputs, scale inputs and ALL parameters must be checked and
changed to proper values to match the scale. Recalibration of the scale is required.

EI-1000: [DOWN ARROW] + [SELECT] + [UP ARROW]
EI-2000: [LEFT UP ARROW] + [LEFT SELECT] + [RIGHT SELECT]




Load typical settings for the selected scales.

This function will load a default scale calibration and setup scale parameters depending on
the P100, P200, P300 and P400 selections. The 4-20mA analog output calibration (not full
scale) is not altered, but one should check the P6xx parameters to insure that they are set to
their proper settings. Recalibration of the scale is required.

EI-1000: [DOWN ARROW] + [UP ARROW]
EI-2000: [LEFT SELECT] + [RIGHT SELECT]




Display test

This function illuminates all 7-segment LED displays and indicator (e.g., gross & remaining)
LEDs.

EI-1000: [ZERO] + [DOWN ARROW]

Exit: [RIGHT ARROW]

EI-2000: [LEFT ZERO] + [RIGHT ZERO]

Exit: [LEFT UP ARROW]




I/O Test mode

This function cycles the 4-20mA outputs and relays. Also, the keypad pushbuttons, DIP
switches and remote input (TB6, IN) functionality can be verified, as well.

EI-1000: [DOWN ARROW] + [RIGHT ARROW]

Exit: [ZERO] + [DOWN ARROW]

EI-2000: [RIGHT SELECT] + [RIGHT UP ARROW]

Exit: [RIGHT ZERO] + [RIGHT DOWN ARROW]