EVCO EVB1256N9D User Manual

Page 79

Advertising
background image

EVCO S.p.A.

EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134

page 79 of 92

14

ALARMS

14.1

Alarms

The following table shows the meaning of the alarm codes of the device.

CODE

MEANING

AL

Minimum alarm temperatures (HACCP alarms)

Solutions:

-

check the temperature associated to the alarm; see parameters A0, A1 and A2

Main consequences:

-

if parameter A0 is set at 0, the device will store the alarm

-

the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)

AH

Maximum temperature alarm (HACCP alarms)

Solutions:

-

check the room temperature or CPT temperature; see parameters A4 and A5

Main consequences:

-

the device will memorise the alarm

-

the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)

id

Door micro switch input alarm (HACCP alarms)

Solutions:

-

check the causes of the activation of the input; see parameters i0 and i1

Main consequences:

-

the effect established with the parameter i0

-

if parameter i4 is set at 1, the device will store the alarm, provided parameter i2 is not set at -1

-

the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)

PF

Power supply cut-off alarm (HACCP alarm)

Solutions:

-

check the causes triggering the power supply cut-off; see parameters A10 and A12

-

press a key to restore normal display

Main consequences: Main consequences:

-

if the interruption lasts longer than the time established with parameter A10, the device will store the alarm

-

the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)

iA

Multifunction and Multifunction 2 input alarm

Solutions:

-

check the causes of the activation of the input; see parameters i5, i6, i15 and i16

Main consequences:

-

the effect established with the parameters i5 and i15

-

the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)