EVCO EVB1256N9D User Manual

Page 87

Advertising
background image

EVCO S.p.A.

EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134

page 87 of 92

Humidity for use:

from 10 to 90 % relative humidity without condensate.

Command device pollution situation:

2.

Height at which it is used:

from 0 to 2,000 m (from 0 to 6,591 ft).

Height at which it can be transported:

from 0 to 3,048 m (from 0 to 10,000 ft).

Environmental standards:

-

RoHS 2011/65/CE

-

WEEE 2012/19/EU

-

REACH (CE) regulation n. 1907/2006.

EMC standards:

-

EN 60730-1

-

IEC 60730-1.

Power supply:

115... 230 VAC (+10 %, -15 %), 50/60 Hz (±3 Hz), 35 VA max.

non insulated, supplied by a class 2 circuit.

The maximum phase current allowed is 16 A.

Magneto-thermal switch:

according to model (230 VAC, In 16 A, Icn 4.500 A, unipolar +

neutral, for wires up to 2,5 mm² (0.0387 in²).

Differential magneto-thermal circuit breaker:

according to model (230 VAC, In 16 A, Icn 4.500 A, Id 300 mA,

unipolar + neutral, for wires up to 2,5 mm² (0.0387 in²).

Remote control switch for three-phase defrost elements

management:

according to model (230 VAC, Ie 9 A, Ui 690 V, Uimp 6 KV, Ith

20 A, 2,2 KW in AC3 at 230 VAC with ta 55 °C, three poles +

neutral, for wires up to 2,5 mm² (0,0387 in²).

Control device grounding method:

with ground terminal

Rated impulse voltage:

4 KV.

Overvoltage category:

III.

Class and structure of software:

A.

Real time clock:

incorporated (with lithium secondary battery).

Battery autonomy without power supply: 6 months.

Battery recharging time: 24 h (the battery is recharged through

the device power supply).

Drift: ≤ 30 s/month at 25 °C (77 °F).