EVCO EVB1256N9D User Manual

Page 83

Advertising
background image

EVCO S.p.A.

EVBOX1 | Installation guide ver. 1.3 | Code 144BOX1E134

page 83 of 92

Pr5

Vapour pressure probe error

Solutions:

-

check that the probe is the 4-20 mA type

-

check the device-probe connection

-

check the vapour pressure

Main consequences:

-

the electronic expansion valve will be open the percentage set with parameter h17

-

the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)

Pr4

Evaporation temperature probe error

Solutions:

-

check that the probe is the PTC, NTC or Pt 1000 type; see parameter P0

-

check the device-probe connection

-

check room/inlet air temperature

Main consequences:

-

the electronic expansion valve will be open the percentage set with parameter h17

-

the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)

rtc

Clock error

Solutions:

-

set the date, time and day of the week

Main consequences:

-

if parameter d8 is set at 4, the device will operate as if it were set at 0

-

the “HACCP” function will not provide information regarding the date and hour in which the alarm was

signalled

-

the “energy saving” function n real time function will not be activated in real time

-

the alarm output will be activated (provided that parameter u1 and/or parameter u11 is set at 3)

When the cause of the error disappears, the device restores normal operation, except for clock error (“rtc” code), which requires the

date, time and day of the week set.