EVCO EPU2LXP1CH Installer manual User Manual

Page 103

Advertising
background image

EVCO S.p.A.

c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104

page 103 of 120

ance ( Low )

1/20

00

2000

2068

3.14.0

7

0x0649

1610

PM90_Last_mainten
ance ( High )

0x064A

1611

PM11a16_EnabMan
ual_Comp[0]

0

0

1

PM11 - Enable compressors manual operation

R/W

0x064B

1612

PM11a16_EnabMan
ual_Comp[1]

0

0

1

PM11 - Enable compressors manual operation

R/W

0x064C

1613

PM11a16_EnabMan
ual_Comp[2]

0

0

1

PM11 - Enable compressors manual operation

R/W

0x064D

1614

PM11a16_EnabMan
ual_Comp[3]

0

0

1

PM11 - Enable compressors manual operation

R/W

0x064E

1615

PM11a16_EnabMan
ual_Comp[4]

0

0

1

PM11 - Enable compressors manual operation

R/W

0x064F

1616

PM11a16_EnabMan
ual_Comp[5]

0

0

1

PM11 - Enable compressors manual operation

R/W

0x0650

1617

PM21a26_ForceCom
p[0]

0

0

1

R/W

0x0651

1618

PM21a26_ForceCom
p[1]

0

0

1

R/W

0x0652

1619

PM21a26_ForceCom
p[2]

0

0

1

R/W

0x0653

1620

PM21a26_ForceCom
p[3]

0

0

1

R/W

0x0654

1621

PM21a26_ForceCom
p[4]

0

0

1

R/W

0x0655

1622

PM21a26_ForceCom
p[5]

0

0

1

R/W

0x0656

1623

PM35_EnabManual_
Pump1

0

0

1

PM35 - Enable pump 1 manual operation

R/W

0x0657

1624

PM36_EnabManual_
Pump2

0

0

1

PM36 - Enable pump 2 manual operation

R/W

0x0658

1625

PM37_ForceManual_
Pump1

0

0

1

PM37 - Force pump 1

R/W

0x0659

1626

PM38_ForceManual_
Pump2

0

0

1

PM38 - Force pump 1

R/W

0x065A

1627

PM45_EnabManual_
SourcePump1

0

0

1

PM45 - Enable cond pump 1 manual operation

R/W

0x065B

1628

PM46_EnabManual_
SourcePump2

0

0

1

PM46 - Enable cond pump 2 manual operation

R/W

0x065C

1629

PM47_ForceManual_
SourcePump1

0

0

1

PM47 - Force cond pump 1

R/W

0x065D

1630

PM48_ForceManual_
SourcePump2

0

0

1

PM48 - Force cond pump 2

R/W

0x065E

1631

PM51_EnabManual_
FanC1

0

0

1

PM51 - Enable the manual/automatic operation of
the condensing fan in Circuit # 1

R/W

0x065F

1632

PM52_EnabManual_
FanC2

0

0

1

PM52 - Enable the manual/automatic operation of
the condensing fan in Circuit # 2

R/W

0x0660

1633

PM61_ForzaturaInv
Fan_C1

0.00

0.00

100.00

R/W

0x0661

1634

PM62_ForzaturaInv
Fan_C2

0.00

0.00

100.00

R/W

0x0662

1635

PM63_ForzaturaInv

0

0

1

PM63 - Manual operation condensing fan Circuit # 1

R/W