PV13

Setpoint HiSH (2)

15.0

10.0

40.0

K

CO-V

PV14

Setpoint LOP (2)

-40.0

-40.0

40.0

K

CO-V

PV15

Setpoint MOP 2)

40.0

-40.0

40.0

K

CO-V

PV16

PID –proportional band (2)

7.0

1.0

100.0

K

CO-V

PV17

PID –integraltime (2)

120

0

999

sec

CO-V

PV18

PID –derivativetime (2)

120

0

999

sec

CO-V

PV19

Start-up delay (2)

5

1

255

sec

CO-V

PV20

Start-up position (2)

50.00

0.00

100.00

%

CO-V

PV21

Stabilization time

0

0

255

sec

CO-V

PV22

Stabilization position

100.00

0.00

100.00

%

CO-V

PV23

Operation mode:

0= SH algo

1= Manual

0

0

1

CO-V

PV24

Manual position

0.00

0.00

100.00

%

CO-V

PV25

SetSH parameters:

0= set1

1= set2

0

0

1

CO-V

PV26

Relay function:

0= Disabled

1=Enabled: any alarm

2=Enabled: probe error

3= LoSH alarm

4= MOP alarm

5= valve alarm

6= solenoid valve

7= solenoid valve + alarms

8= resyncro

6

0

8

CO-V

PV27

Probe type 3:

0= NTC

1= PT1000

0

0

1

CO-V

PV28

Probe type 4:

0= 4..20mA (0.5 – 8)

1= 4..20mA (0 – 30)

2= 0-5V (0 – 7)

3= 0-5V (0 – 25)

4= 0-5V (0 – 60)

5= scaling

0

0

1

CO-V

PV29

Probe type 1:

1= PTC

2= NTC

3= 0..20mA

4= 4..20mA

5= 0-5V

6= 0-10V

7= PT1000

8= NTC K2

9= NTC K3

5

1

9

CO-V

PV30

Probe type 2:

1= PTC

2= NTC

3= 0..20mA

4= 4..20mA

5= 0-5V

6= 0-10V

2

1

9

CO-V