c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104

page 28 of 120

PC46

Pressure set point for high-

temperature pressure-switch control

27.0

0.0

45.0

Bar

IS-R

PC47

Pressure differential for high-

temperature pressure-switch control

2.0

0.0

5.0

Bar

IS-R

PC48

External high temperature threshold

for pressure-switch control

12.0

-30.0

23.0

°C

IS-R

PC49

Min. time for maintaining pressure-

switch partialization

10

0

99

Min.

IS-R

PC50

Enabling of low-temperature

pressure-switch control (heat pump)

No (0)

No (0)

Yes (1)

IS-R

PC51

Pressure setpoint for low-temperature

pressure-switch control

3.2

0.0

10.0

Bar

IS-R

PC52

Pressure differential for low-

temperature pressure-switch control

2.0

0.0

10.0

Bar

IS-R

PC53

External low temperature threshold

for pressure-switch control

-5.0

-10.0

5.0

°C

IS-R

PC54

Outlet water high-temperature

threshold for pressure-switch control

48.0

30.0

70.0

°C

IS-R

PC55

Delay for partialization from low

pressure alarm

900

0

999

Sec.

IS-R

PC61

Summer commutation set point

20.0

PC62

70.0

°C

IS-R

PC62

Winter commutation set point

10.0

0.0

PC61

°C

IS-R

PC64

Max. dynamic offset compared to

summer set point (chiller)

-10.0

-20.0

20.0

°C

IS-R

PC65

Compensation start temperature for

dynamic summer set point

30.0

-15.0

PC66

°C

IS-R

PC66

Compensation stop temperature for

dynamic summer set point

60.0

PC65

70.0

°C

IS-R

PC67

Max. dynamic offset compared to

winter set point (heat pump)

10.0

-20.0

20.0

°C

IS-R

PC68

Compensation start temperature for

dynamic winter set point

0.0

-15.0

PC69

°C

IS-R

PC69

Compensation stop temperature for

dynamic winter set point

30.0

PC68

70.0

°C

IS-R

PC70

Function limit management:

0 = Heat pump only

1 = Auxiliary output

2 = Auxiliary output and heat pump

0

0

2

IS-R

PC71

Function limit set point

-7.0

-30.0

30.0

°C

IS-R

PC72

Function limit differential

4.0

0.1

10.0

°C

IS-R

PC80

Enabling of control upon request

No (0)

No (0)

Sì (1)

IS-R

PC81

Summer setpoint controlupon request

15.0

-15.0

70.0

°C

IS-R

PC82

Winter setpoint control upon request

45.0

-15.0

70.0

°C

IS-R

PC83

Summer differential control upon

request

4.0

0.1

10.0

°C

IS-R

PC84

Winter differential control upon request

4.0

0.1

10.0

°C

IS-R

PC85

Delayed control upon request

5

0

999

Sec

IS-R

FANS

PF01

Condenser control type

0

0

1

IS-F

0=Modulating

control

1=Single

stage control

PF02

It gives the choice to enable fan

Yes (1)

No (0)

Yes (1)

IS-F