EVCO EPU2LXP1CH Installer manual User Manual

Page 17

Advertising
background image

EVCO S.p.A.

c-pro 3 micro CHIL | Application manual ver. 1.0 | Codice 144CP3CHE104

page 17 of 120

Pressing ENTER on the label causes the value of the relative status to be displayed;pressing ESC brings you back to the general menu

screen. This menu is not protected by a password.

6.4.1

Meaning of LED (only for display LED)

The LED display offers several icons that display particular statuses of the unit:

OnOff. If on, it means that the unit has no power; if off, it means that the unit is on; if on with slow flashing light, it means

that the unit is not being powered by the Scheduler; if on with fast flashing light, it means that the unit is not being powered

by the Supervisor or Digital Input.

Snow. If on, summer/winter function (seeparameter PH53); if on and flashing, the free-cooling function is active.

Sun. If on, summer/winter function (see parameter PH53).

Alarm. If on, the function indicates the presence of alarms; if on and flashing, it indicates the presence of new alarms not

displayed yet; if off, there are no alarms.

Defrost. If on, it means that defrosting is active in one of the 2 circuits; if on and flashing, it means that draining is active in

one of the2 circuits

Maintain. If on, it means that at least one device is functioning manually; if on and flashing, it means that a “device

operating hours” alarm is active.

Compressor 1. If on, it means that at least one compressor of circuit 1 is active; if off, it means that no circuit compressors

are active; if on and flashing slowly, it means that a circuit compressor is in the alarm state; if on and flashing quickly, it

means that a circuit compressor is in manual mode.

Compressor 2. If on, it means that at least one compressor of circuit 2 is active; if off, it means that no circuit compressors

are active; if on and flashing slowly, it means that a circuit compressor is in the alarm state; if on and flashing quickly, it

means that a circuit compressor is in manual mode.

Pump. If on, it means that a heat sink pump is active; if off, it means that no pumps are active; if on and flashing slowly, it

means that a pump is in the alarm state; if on and flashing quickly, it means that a pump is in manual mode.

Fan. If on, it means that one fan is active; if off, it means that no fans are active; if on and flashing slowly, it means that a

fan is in the alarm state; if on and flashing quickly, it means that a fan is in manual mode.

Heaters: If on, it means that the strength of the antifreeze mechanism (heat sink or source) is active; if off, it means that no

antifreeze mechanisms are active; if on and flashing slowly, it means that an antifreeze mechanism is in the alarm state.

EVCO. Icon linked to the functioning of parameter PH52.

Advertising
This manual is related to the following products: