When planning a radiant heating
installation, refer to Table 1 to select the
application and type of environment
you wish to heat. Table 2 shows the
area that can be heated by a single
Sunslim radiant heater in 3kW and
2kW variants.

Note: Heating areas can be overlapped
to achieve the necessary heating index.

0.3

0.1

2.0

2.0

0.5

Sunslim - Minimum

mounting distances

(metres)

Heating index

3kW

2kW

H

L

W

H

L

W

10

4.0

5.24

5.49

3.3

4.11

4.53

12

3.6

4.88

4.94

3.0

3.84

4.12

14

3.2

4.51

4.39

2.7

3.57

3.70

16

3.5

4.33

4.12

2.5

3.38

3.43

18

2.8

4.14

3.84

-

-

-

H = mounting height (determined by on-site requirements) L = length of the heated area W = width of the heated area

Applications

Heating Index

Offices, canteens,

10-14

waiting rooms, entrance

halls, dressing rooms

Shops, meeting halls,

12-16

recreation rooms, clubs

workshops, garages,

14-18

public buildings

Warehouses, loading bays,

16-20

hangars

Churches

18-20

Use the following procedure when
planning a Sunquartz heating
installation for buildings having a floor
area of up to 500m

2

.

• Make a scaled plan of the area to be

heated, noting possible mounting heights
and positions

• Determine the overall heating requirements

WxYxK = Total kW loading

1000

Key:
W= Length to be heated in metres

Y = Width to be heated in metres

K = Intensity watts per m

2

, determined

from Heating Index Table 1

• Determine the number of Sunquartz

heaters by dividing the kW rating of the
selected units into the total kW loading
from stage 2

Model

Spare tube reference

Min mounting distances

A

B

C

Sunquartz 1.5kW

85 821421

1,800

300

300

Sunquartz 2.0kW

85 822171

2,500

300

300

Sunquartz 3.0kW 2 lamp

85 821421

3,000

500

500

Sunquartz 3.0kW 3 lamp

85 821421

3,000

500

500

Sunquartz 4.0kW

85 822171

3,000

500

500

Sunquartz 4.5kW

85 821421

3,000

500

500

Sunquartz 6.0kW

85 822171

4,000

500

500

Sunquartz -

Recommended Applications:

Heating Index (K)

130 - 170

Shops, meeting halls,

recreation rooms, clubs

150 - 170

Offices, canteens,

waiting rooms,

entrance halls

150 - 200

Workshops, garages,

public buildings

180 - 220

Warehouses, loading bays,

hangars

220 - 240

Churches

Sizing Guide
Commercial space heaters

Sunslim radiant heaters

Table 1 - Sunslim heating index

Table 2 - Sunslim heated area

Sunquartz radiant heaters

Table 1 - Sunquartz heating index

B

C

A

30" Min.

Table 2 - Sunquartz heated area

45

+44 (0) 1733 456789 www.creda-heating.co.uk

Advertising