General, Air flow – Chromalox PF455-3 User Manual

Page 3

Advertising
background image

7. Installation in duct larger than heater. For installation where the

duct dimensions exceed the insert type heater dimensions, the
area beyond the heater dimensions must be filled with wire
mesh, expanded or perforated sheet metal of 50% open area as
shown in Figure 11. This will maintain a uniform air velocity
across the face of the duct.

8. Installation with flexible duct. Where a duct heater must be

installed near a flexible duct connection, be certain that a 4’
minimum distance between the duct heater and the flexible
connector exists and that the connector is suitable for 195°F
temperature. (Refer to Figure 12).

9. Do not install duct heater outdoors. Duct heaters cannot be

installed with rooftop equipment where they are exposed to the
weather.

10. Installation with dampers or filters. Maintain at least 4’ dis-

tance between duct heater and damper, filter frames, or other
similar obstructions. (Refer to Figure 13).

Clearance: Zero clearance between duct heater and combustible
materials such as wood is permissible. However, adequate clear-
ance must be provided around terminal box for proper ventilation
and future service accessibility.

4 Ft.
Min.

Damper

Air Flow

Top of Duct

Duct

Heater

4 Ft.
Min.

Air

Flow

Duct Heater

Flexible Duct

(Must be suitable

for 195°F)

Inner Baffle

Insert Type
Duct Heater

Remove Bracket and
Use Sheetmetal Screws
Thru Same Holes into Duct.

Oversized Duct

Perforated Metal
(50% Open Area)

-3-

GENERAL

Flow through duct heater must never drop below the minimum

air velocity shown on duct heater nameplate. If the air handling
system includes filters, they must be cleaned whenever necessary
in order to maintain air flow above the minimum, otherwise poor
temperature control and discomfort will result.

If air flow is poorly distributed within the duct, deflector vanes

must be added to provide correction.

The minimum air velocities shown on the nameplate are not to

be considered average readings. Do not add various velocities
taken across the face of the duct, find an average value, and com-
pare it to the minimum velocity shown on the heater nameplate.

The minimum air velocity refers to any point along the face of

the duct heater when checking duct velocities, no velocity can be
below that sown on the heater nameplate (remembering inlet air
temperature). Velocities are best checked with an anemometer, tak-
ing numerous readings along the horizontal and vertical centerline
of the duct heater at the location prior to installation or slightly up
stream from the heater after installation. (Refer to Figure 14).
Large ducts will require additional readings taken at locations in
addition to the centerline.

Incoming Air Temperature: Incoming air temperature entering
the duct heater must not exceed 100°F.

Duct Heater

Velocity
Profile

Air Flow

AIR FLOW

Example: 500 FT./MIN. Minimum Air Velocity on Heater Nameplate.

600

200x

500

400x

700

800

Velocity

600

Velocity

900

Profile

900

Profile

600

FT./MIN.

700

FT./MIN.

700

600

200x

500

300x
400x

RIGHT:

500 FT./MIN. MINIMUM

WRONG:

9 4500 = 500 FT./MIN. AVERAGE

X – below 500 FT./MIN.

Figure 11

Figure 12

Figure 13

Figure 14

Advertising