WIRING

WIRING DIAGRAM

RENEWAL PARTS IDENTIFICATION

1. Connect heater only to the voltage, frequency and phase spec-

ified on the nameplate.

2. All wiring should be done according to local and National

Electric Codes.

3. Make supply connections to marked heater terminals using

wire suitable for 75°C. (Type RH-RW or equivalent).

4. Conduit attachment to heater:

a. Run conduit(s) to conduit entrance plate. (See Figure 1).
b. Mark plate where conduit(s) will enter plate.
c. Remove screws and plate.
d. Punch conduit entrance plate with a hole(s) to accommo-

date the required conduit(s).

e. Reinstall plate and install conduit(s) to plate.

Fan Interlock. The fan circuit must be interlocked with the

control circuit of the heater. Refer to the wiring diagram in the
heater terminal box.

Hazard of electrical shock. Any installation involv-
ing electric heaters must be grounded to earth to
eliminate shock hazard.

Hazard of severe shock. Disconnect all power to
heater before servicing.

Control Ratings

Manual Limit Control

Automatic Limit Control

Pilot

Non-Inductive

Pilot

Non-Inductive

Volts

Duty

Rating

Duty

Rating

120

125 VA

3000 Watts

125 VA

3000 Watts

208

125 VA

5200 Watts

125 VA

5200 Watts

240

125 VA

6000 Watts

125 VA

6000 Watts

277

125 VA

6925 Watts

125 VA

6925 Watts

The appropriate wiring diagram

will be supplied with each heater.

Contact your local Chromalox Sales Office with Complete heater catalog number or part number.

-6-

Static equalizers
(not shown) maintain
uniform air flow
across the heater
face when individual
fintubes are omitted.

Air Flow Switch

Main Disconnect

Conduit Entrance Plate

Contactor

Fusing

Air Flow Switch Automatic and Manual Reset

(not shown)

Fintube Heating

Element

Transformer Fusing

Transformer

Typical DHIF Duct Heater