INSTALLATION INSTRUCTIONS

25

Prior to installation, ensure that the local distribution conditions (nature of the gas and gas
pressure) and the adjustment conditions are compatible. The adjustment conditions for this
appliance are stated on the data badge which is fitted behind the bottom of the main oven door
seal. This appliance is not designed to be connected to a combustion products evacuation device.
It must be installed and connected in accordance with current installation regulations. particular
attention should be given to the relevant requirements regarding ventilation.

MODEL NUMBERS CB01G

Category I

2H

(GB. IE)

These models are set to burn NATURAL GAS (G20) only.

GAS SAFETY (INSTALLATION & USE) REGULATIONS

It is the law that all gas appliances are installed by competent persons in accordance with
the current edition of the above regulations. It is in your interest and that of safety to
ensure compliance with the law.

In the UK, CORGI registered installers work to safe standards of practice. The
appliance must also be installed in accordance with BS 6172. Failure to install the
appliance correctly could invalidate the warranty liability claims and could lead to
prosecution.

LOCATION

The appliance may be located in a kitchen, kitchen/diner or a bed-sitting room, but not
in a room containing a bath or shower. The appliance must not be installed in a bed-
sitting room of less than 20m

3

.

PROVISION FOR VENTILATION

The room containing the appliance should have an air supply in accordance with
BS 5440: Part 2.

The room must have an opening window or equivalent; some rooms may also require a
permanent vent. If the room has a volume between 5 and 10m

3

, it will require an air vent

of 50cm

2

effective area unless it has a door which opens directly to outside. If the room

has a volume of less than 5m

3

, it will require permanent air vent of 100cm

2

effective area.

If there are other fuel burning appliances in the same room, BS 5440: Part 2 should be
consulted to determine air vent requirements.