Fig. 56 -- EconoMi$er IV Functional View

EconoMi$er IV

Table 11 provides a summary of Economizer IV.

Troubleshooting instructions are enclosed.

A functional view of the EconoMi$er is shown in 56.

Typical settings, sensor ranges, and jumper positions are

also shown. An EconoMi$er IV simulator program is

available from Carrier to help with EconoMi$er IV

training and troubleshooting.
EconoMi$er IV Standard Sensors
Outdoor Air Temperature (OAT) Sensor
The outdoor air temperature sensor (HH57AC074) is a 10

to 20 mA device used to measure the outdoor-air

temperature. The outdoor-air temperature is used to

determine when the EconoMi$er IV can be used for free

cooling. The sensor is factory-installed on the

EconoMi$er IV in the outdoor airstream. (See Fig. 55.)

The operating range of temperature measurement is 40_ to

100_F (4_ to 38_C). See Fig. 55.
Supply Air Temperature (SAT) Sensor
The supply air temperature sensor is a 3 K thermistor

located at the inlet of the indoor fan. (See Fig. 57.) This

sensor is factory installed. The operating range of

temperature measurement is 0° to 158_F (--18_ to 70_C).

See Table 5 for sensor temperature/resistance values.

SUPPLY AIR

TEMPERATURE

SENSOR

MOUNTING

LOCATION

SUPPLY AIR

TEMPERATURE

SENSOR

C06033

Fig. 57 -- Supply Air Sensor Location

The temperature sensor looks like an eyelet terminal with

wires running to it. The sensor is located in the “crimp

end” and is sealed from moisture.
Outdoor Air Lockout Sensor
The EconoMi$er IV is equipped with an ambient

temperature lockout switch located in the outdoor

airstream which is used to lock out the compressors below

a 42_F (6_C) ambient temperature. (See Fig. 52.)
EconoMi$er IV Control Modes

IMPORTANT:

The optional EconoMi$er2 does not include

a controller. The EconoMi$er2 is operated by a 4 to 20
mA signal from an existing field-supplied controller (such
as PremierLink™ control). See Fig. 54 for wiring

information.
Determine the EconoMi$er IV control mode before set up

of the control. Some modes of operation may require

different sensors. (See Table 12.) The EconoMi$er IV is

supplied from the factory with a supply--air temperature

sensor and an outdoor-- air temperature sensor. This allows

for operation of the EconoMi$er IV with outdoor air dry

bulb changeover control. Additional accessories can be

added to allow for different types of changeover control

and operation of the EconoMi$er IV and unit.
Outdoor Dry Bulb Changeover
The standard controller is shipped from the factory

configured for outdoor dry bulb changeover control. The

outdoor air and supply air temperature sensors are

included as standard. For this control mode, the outdoor

temperature is compared to an adjustable setpoint selected

on the control. If the outdoor-air temperature is above the

setpoint, the EconoMi$er IV will adjust the outside air

dampers to minimum position. If the outdoor-air

temperature is below the setpoint, the position of the

outside air dampers will be controlled to provided free

cooling using outdoor air. When in this mode, the LED

next to the free cooling setpoint potentiometer will be on.

The changeover temperature setpoint is controlled by the

free cooling setpoint potentiometer located on the control.

(See Fig. 58.) The scale on the potentiometer is A, B, C,

50TC