Carrier 50TCA04-A07 User Manual

Page 38

Advertising
background image

38

timeclock function in place of the jumper between TR and

N. (See Fig. 52.) When the timeclock contacts are closed,

the EconoMi$er IV control will be in occupied mode.

When the timeclock contacts are open (removing the 24--v

signal from terminal N), the EconoMi$er IV will be in

unoccupied mode.
Demand Control Ventilation (DCV)
When using the EconoMi$er IV for demand controlled

ventilation, there are some equipment selection criteria

which should be considered. When selecting the heat

capacity and cool capacity of the equipment, the

maximum ventilation rate must be evaluated for design

conditions. The maximum damper position must be

calculated to provide the desired fresh air.
Typically the maximum ventilation rate will be about 5 to

10% more than the typical cfm required per person, using

normal outside air design criteria.
A proportional anticipatory strategy should be taken with

the following conditions: a zone with a large area, varied

occupancy, and equipment that cannot exceed the required

ventilation rate at design conditions. Exceeding the

required ventilation rate means the equipment can

condition air at a maximum ventilation rate that is greater

than the required ventilation rate for maximum

occupancy. A proportional-anticipatory strategy will cause

the fresh air supplied to increase as the room CO

2

level

increases even though the CO

2

setpoint has not been

reached. By the time the CO

2

level reaches the setpoint,

the damper will be at maximum ventilation and should

maintain the setpoint.
In order to have the CO

2

sensor control the economizer

damper in this manner, first determine the damper voltage

output for minimum or base ventilation. Base ventilation

is the ventilation required to remove contaminants during

unoccupied periods. The following equation may be used

to determine the percent of outside air entering the

building for a given damper position. For best results there

should be at least a 10 degree difference in outside and

return-air temperatures.

(T

O x

OA

) + (TR

x

RA

) =T

M

100

100

T

O

= Outdoor-Air Temperature

OA = Percent of Outdoor Air
T

R

= Return-Air Temperature

RA = Percent of Return Air
T

M

= Mixed-Air Temperature

Once base ventilation has been determined, set the

minimum damper position potentiometer to the correct

position.
The same equation can be used to determine the occupied

or maximum ventilation rate to the building. For example,

an output of 3.6 volts to the actuator provides a base

ventilation rate of 5% and an output of 6.7 volts provides

the maximum ventilation rate of 20% (or base plus 15 cfm

per person). Use Fig. 64 to determine the maximum

setting of the CO

2

sensor. For example, an 1100 ppm

setpoint relates to a 15 cfm per person design. Use the

1100 ppm curve on Fig. 64 to find the point when the CO

2

sensor output will be 6.7 volts. Line up the point on the

graph with the left side of the chart to determine that the

range configuration for the CO

2

sensor should be 1800

ppm. The EconoMi$er IV controller will output the 6.7

volts from the CO

2

sensor to the actuator when the CO

2

concentration in the space is at 1100 ppm. The DCV

setpoint may be left at 2 volts since the CO

2

sensor

voltage will be ignored by the EconoMi$er IV controller

until it rises above the 3.6 volt setting of the minimum

position potentiometer.
Once the fully occupied damper position has been

determined, set the maximum damper demand control

ventilation potentiometer to this position. Do not set to the

maximum position as this can result in over-ventilation to

the space and potential high humidity levels.
CO

2

Sensor Configuration

The CO

2

sensor has preset standard voltage settings that

can be selected anytime after the sensor is powered up.

(See Table 12.)
Use setting 1 or 2 for Carrier equipment. (See Table 12.)

1. Press Clear and Mode buttons. Hold at least 5

seconds until the sensor enters the Edit mode.

2. Press Mode twice. The STDSET Menu will appear.

Table 12 – EconoMi$er IV Sensor Usage

APPLICATION

ECONOMI$ER IV WITH OUTDOOR AIR

DRY BULB SENSOR

Accessories Required

Outdoor Air

Dry Bulb

None. The outdoor air dry bulb sensor

is factory installed.

Differential

Dry Bulb

CRTEMPSN002A00*

Single Enthalpy

HH57AC078

Differential

Enthalpy

HH57AC078

and

CRENTDIF004A00*

CO

2

for DCV

Control using a

Wall-Mounted

CO

2

Sensor

33ZCSENCO2

CO

2

for DCV

Control using a

Duct-Mounted

CO

2

Sensor

33ZCSENCO2†

and

33ZCASPCO2**

O

R

CRCBDIOX005A00††

*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used

on many different base units. As such, these kits may contain parts

that will not be needed for installation.
† 33ZCSENCO2 is an accessory CO

2

sensor.

** 33ZCASPCO2 is an accessory aspirator box required for duct-

mounted applications.
†† CRCBDIOX005A00 is an accessory that contains both

33ZCSENCO2 and 33ZCASPCO2 accessories.

3. Use the Up/Down button to select the preset

number. (See Table 12.)

4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.

The custom settings of the CO

2

sensor can be changed

anytime after the sensor is energized. Follow the steps

below to change the non-standard settings:

1. Press Clear and Mode buttons. Hold at least 5

seconds until the sensor enters the Edit mode.

2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD

menu and press Enter.

4. Use the Up/Down button to toggle through each of

the nine variables, starting with Altitude, until the

desired setting is reached.

50TC

Advertising