Warning – Carrier 50TCA04-A07 User Manual

Page 41

Advertising
background image

41

4. Verify the following conditions:

a. Make sure that condenser--fan blade are correctly

positioned in fan orifice. See Condenser--Fan

Adjustment section on page 11 for more details.

b. Make sure that air filter(s) is in place.

c. Make sure that condensate drain trap is filled

with water to ensure proper drainage.

d. Make sure that all tools and miscellaneous loose

parts have been removed.

START--UP, GENERAL

Unit Preparation

Make sure that unit has been installed in accordance with

installation instructions and applicable codes.

Return--Air Filters

Make sure correct filters are installed in unit (see

Appendix II -- Physical Data). Do not operate unit without

return--air filters.

Outdoor--Air Inlet Screens

Outdoor--air inlet screen must be in place before operating

unit.

Compressor Mounting

Compressors are internally spring mounted. Do not loosen

or remove compressor hold down bolts.

Internal Wiring

Check all electrical connections in unit control boxes.

Tighten as required.

Refrigerant Service Ports

Each unit system has two 1/4” SAE flare (with check

valves) service ports: one on the suction line, and one on

the compressor discharge line. Be sure that caps on the

ports are tight.

Compressor Rotation

On 3--phase units with scroll compressors, it is important

to be certain compressor is rotating in the proper

direction. To determine whether or not compressor is

rotating in the proper direction:

1. Connect service gauges to suction and discharge pres-

sure fittings.

2. Energize the compressor.
3. The suction pressure should drop and the discharge

pressure should rise, as is normal on any start--up.

If the suction pressure does not drop and the discharge

pressure does not rise to normal levels:

1. Note that the evaporator fan is probably also rotating

in the wrong direction.

2. Turn off power to the unit and install lockout tag.
3. Reverse any two of the unit power leads.
4. Re--energize to the compressor. Check pressures.

The suction and discharge pressure levels should now

move to their normal start--up levels.

NOTE: When the compressor is rotating in the wrong

direction, the unit will make an elevated level of noise
and will not provide cooling.

Cooling

Set space thermostat to OFF position. To start unit, turn on

main power supply. Set system selector switch at COOL

position and fan switch at AUTO. position. Adjust

thermostat to a setting below room temperature.

Compressor starts on closure of contactor.

Check unit charge. Refer to Refrigerant Charge section on

page 7.

Reset thermostat at a position above room temperature.

Compressor will shut off. Evaporator fan will shut off

after a 30--second delay.

TO SHUT OFF UNIT

Set system selector switch at OFF position. Resetting

thermostat at a position above room temperature shuts

unit off temporarily until space temperature exceeds

thermostat setting.

Heating

To start unit, turn on main power supply.

Set system selector switch at HEAT position and set

thermostat at a setting above room temperature. Set fan at

AUTO position.

First stage of thermostat energizes the first--stage electric

heater elements; second stage energizes second--stage

electric heater elements, if installed. Check heating effects

at air supply grille(s).

If electric heaters do not energize, reset limit switch

(located on evaporator--fan scroll) by pressing button

located between terminals on the switch.

TO SHUT OFF UNIT -- Set system selector switch at OFF

position. Resetting thermostat at a position below room

temperature temporarily shuts unit off until space

temperature falls below thermostat setting.

Ventilation (Continuous Fan)

Set fan and system selector switches at ON and OFF

positions,

respectively.

Evaporator

fan

operates

continuously to provide constant air circulation.

START--UP, PREMIERLINK CONTROLS

ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal

injury or death.
The unit must be electrically grounded in accordance

with local codes and NEC ANSI/NFPA 70 (American

National Standards Institute/National Fire Protection

Association.)

!

WARNING

50TC

Advertising