Carrier 50TCA04-A07 User Manual

Page 48

Advertising
background image

48

equal to OCSP and Enthalpy = Low then PURGEMP =
100%.

S

If the OAT < NTLO then PURGEMP = LTMP (Low
Temperature Minimum Position -- defaults to 10%)

S

If the OAT > 65_F or (OAT ≥ NTLO and OAT > OCSP)
or Enthalpy = High then PURGEMP = HTMP (High
Temperature Minimum Position defaults to 35%).

The LTMP and HTMP are user adjustable values from 0

to 100% in the SETPOINT table. Whenever PURGEMP

results in a number greater than 0%, the IAQ

pre--occupancy purge mode will be enabled turning on the

Indoor Fan Relay and setting the economizer IQMP to the

PURGEMP value. When IAQ pre--occupancy mode is not

active PURGEMP = 0%.

Unoccupied Free Cooling — Unoccupied free cool

function will start the indoor fan during unoccupied times

in order to cool the space with outside air. This function is

performed to delay the need for mechanical cooling when

the system enters the occupied period. Depending on how

Unoccupied Free Cooling is configured, unoccupied mode

can occur at any time in the unoccupied time period or 2

to 6 hours prior to the next occupied time. Once the space

has been sufficiently cooled during this cycle, the fan will

be stopped. In order to perform unoccupied free cooling

all of the following conditions must be met:

S

NTEN option is enabled in the CONFIG configuration
table

S

Unit is in unoccupied state

S

Current time of day is valid

S

Temperature Compensated Start mode is not active

S

COOL mode is not active

S

HEAT mode is not active

S

SPT reading is available

S

OAT reading is available

S

Enthalpy is low

S

OAT > NTLO (with 1_F hysteresis) and < Max Free Cool
setpoint

If any of the above conditions are not met, Unoccupied

Free Cool mode will be stopped, otherwise, the mode will

be controlled as follows:

The NTFC setpoint (NTSP) is determined as NTSP =

(OCSP + OHSP) / 2
The Unoccupied Free Cool mode will be started when:

SPT > (NTSP + 2_F) and SPT > (OAT + 8_F)

The Unoccupied Free Cool mode will be stopped when:

SPT < NTSP or SPT < (OAT + 3_F)

Temperature Compensated Start — This function will run

when the controller is in unoccupied state and will

calculate early start bias time (SBT) based on space

temperature deviation from occupied setpoints in minutes

per degree. The following conditions will be met for the

function to run:

S

Unit is in unoccupied state

S

Next occupied time is valid

S

Current time of day is valid

S

Valid space temperature reading is available (from sensor
or linkage thermostat)

S

Cool Start Bias (KCOOL) and Heat Bias Start (KHEAT)
> 0 in the CONFIG configuration table

The SBT is calculated by one of the following formulas

depending on temperature demand:

If SPT > OCSP then SBT = (SPT -- OCSP) * KCOOL
If SPT < OHSP then SPT = (OHSP -- SPT) * KHEAT.

The calculated start bias time can range from 0 to 255

minutes. When SBT is greater than 0 the function will

subtract the SBT from the next occupied time to calculate

a new start time. When a new start time is reached, the

Temperature Compensated Start mode is started. This

mode energizes the fan and the unit will operate as though

it is in occupied state. Once set, Temperature

Compensated Start mode will stay on until the unit returns

to occupied state. If either Unoccupied Free Cool or IAQ

Pre--Occupancy mode is active when Temperature

Compensated Start begins, their mode will end.

Door Switch — The Door Switch function is designed to

disable mechanical heating and cooling outputs when the

REMOCC contact input is closed (in the ON state) after a

programmed time delay. The fan will continue to operate

based on the current mode and the ASHRAE 90.1 Supply

Fan setting. The delay is programmable from 2 to 20

minutes by setting the Remote Cont/Door Switch decision

in the SERVICE table to a value equal to the number of

minutes desired. When the contact is open (in the OFF

state), the PremierLink controller will resume normal

temperature control.

This application is designed for use in schools or other

public places where a door switch can be installed to

monitor the opening of a door for an extended period of

time. The controller will disable mechanical cooling and

heating when the door is open for a programmed amount

of time.

This function can also be used to monitor a high

condensate level switch when installed on a water source

heat pump to disable mechanic cooling in case of a

plugged evaporator condensate pan drain.

Linkage — The Linkage function in the PremierLink

controller is available for applications using a Linkage

thermostat or the 3V control system. If using the Linkage

thermostat, both the PremierLink controller and the stat

must be on the same CCN bus. When used as the air

source for a 3V control system, the PremierLink controller

is not required to be on the same CCN bus but it is

recommended. Linkage will be active when it is initiated

from the Linkage thermostat or the 3V Linkage

Coordinator through CCN communications and requires

no configuration. Only one device can be linked to the

PremierLink controller.

50TC

Advertising