21 vent/air intake terminal locations, Figure 7 – LAARS IGI-180C - Installation Manual User Manual

Page 21

Advertising
background image

21

VENT/AIR INTAKE TERMINAL LOCATIONS

Direct Vent Terminal Location
Plan the vent system layout so that proper clearances are maintained from plumbing and wiring. Before
the vent is installed, determine the vent pipe termination location as shown below in the Vent Terminal
Location illustration.

Vent/Air Intake Terminal Positions – MINIMUM Dimensions

Figure 7

Canadian

Installations

1

US Installations

2

Canadian

Installations

1

US

Installations

2

A= Clearance

above

grade, veranda,
porch, deck or
balcony

12 inches (30 cm)

12 inches

(30 cm)

H=

Clearance to each side
of center line extended
above meter/regulator
assembly

36 inches (91 cm)

within a height 15 feet

(4.6 m) above the

meter/regulator

assembly

*b

B= Clearance

to

widow or door that
may be opened

36 inches (91 cm)

for appliances >

100,000 Btuh (30

kW)

12 inches (30

cm) for

appliances >

50,000 Btuh (15

kW)

I=

Clearance to service
regulator vent outlet or
oil tank vent

36 inches

(91 cm)

*b

C= Clearance

to

permanently
closed widow

*b

*b

J=

Clearance to non-
mechanical air supply
inlet to building or the
combustion air inlet to
any other appliance

36 inches (91 cm) for

appliances > 100,000

Btuh (30 kW)

12 inches (30 cm)

for appliances >
50,000 Btuh (15

kW).

D= Vertical

clearance

to ventilated soffit
located above the
terminal within a
horizontal
distance of 2 feet
(61 cm) from the
center line of the
terminal

*b

*b

K=

Clearance to a
mechanical air supply
inlet

6 feet

(1.83 m)

3 feet (91 cm)

above if within 10

feet horizontally

E= Clearance

to

unventilated soffit

*b

*b

L=

Clearance above paved
sidewalk or paved
driveway located on
public property

7 feet

(2.13 m)†

*b

F= Clearance

to

outside corner

*b *b

M=

Clearance

under

a

veranda, porch, deck, or
balcony

12 inches (30 cm) ‡

*b

G= Clearance

to

inside corner

36 inches
(91 cm)*a

36 inches
(91 cm)*a

1

In accordance with the current CAN/CGA-B149 Installation Codes.

2

In accordance with the current ANSI Z223.1-(Latest Edition)/NFPA 54 National Fuel Gas Code.

† A vent shall not terminate directly above a sidewalk or paved driveway that is located between
two single-family dwellings and serves both dwellings.

‡ Permitted only if a veranda, porch, deck or balcony is fully open on a minimum of two sides beneath
the floor.
*a) A minimum clearance value determined by testing in accordance with section 2.20.
*b) “Clearance in accordance with local installation codes and the requirements of the gas supplier”.