LAARS Heating Systems

Figure 9. Condensate drain tube outlet.

NOTE: All internal electrical components have

been prewired. No attempt should be made to connect

electrical wires to any other location except the wiring

box designated above.

Wiring connections are indicated on the wiring

diagram (see Figure 10).

3.7 Main Power

Connect a 15 amp, fused, 120-volt supply to the

main power switch (hot leg is connected directly to

switch). Neutral leg is connected directly to the white

wire. Ground wire can be connected to the grounding

screw in the box.

3.8 Temperature Control

Connect the tank aquastat to the red and white/

red wires marked “T”. Do not connect two units to the

same set of aquastat contacts.

SECTION 4.
Start Up

4.1 Filling the System

1.

Open all valves.

2.

Fill 9600 HWG Water Heater and the system

completely.

3.

Purge air from system. Bleed air from 9600

HWG using the air bleed at top of thermostatic

valve inside unit under access plate on top panel.

4.

Set aquastat to call for heat, turn on power at

main switch for 30 seconds, then turn off.

5.

Bleed 9600 HWG Water Heater and system

again. After system is fully purged, the 9600

HWG Water Heater is ready for firing.

4.2 Operation Checklist

1.

Be sure that system has been filled properly (see

above) and is leak tight.

2.

Open gas cock(s) and open manual gas shutoff

valve by turning to “on” position (see Figure 11).

3.

Turn on main switch, set aquastat to call for

heat.

4.

Blower will come on.

5.

NOTE: Burner may not ignite on first attempt

because of air contained in gas lines. In this case

blower will stop after 5 minutes. Should this

happen, turn off main switch. Wait five minutes

and turn on switch again.

If burner fails three times, refer to Service Manual.

6.

After placing the water heater in operation, the

burner safety shutoff device must be tested. To

test, disconnect ignitor plug at ignitor. Attempt

to start appliance. After the burner control has

completed three complete cycles the gas valve

must not open again and the VALVE / FLAME

light on the burner control must flash. Failure to

operate in this manner must be corrected by a

qualified service contractor or gas company.

Safe lighting and other performance criteria were

met with the gas manifold and control assembly

provided on the water heater when it underwent

tests specified in ANSI Z21.10.3-Latest Edition

and CAN / CGA 1 - 4.3 Latest Edition.

CAUTION: Should any pronounced odor of gas

be detected or if the gas burner does not appear

to be functioning in a normal manner, close main

shut off valve and contact your heating

contractor, gas company or factory

representative.

7.

Changing the gas orifice.

A 9600 HWG tune-up kit is available from your

supplier. It contains a larger (marked +) and

smaller orifice (marked -). If the firing rate is

low, install the larger diameter orifice. Shut off

electricity and gas to the unit. Loosen the gas

orifice union (see Figure 12) and move the lower

half of the union far enough to the side to

remove the orifice. Change orifice. Reassemble,

Figure 10. Electrical hook-up.

GRN

BLK

WH

RED (LOW VOLTAGE) - T

WH/RED (LOW VOLTAGE) - T

GROUND

120 VAC LINE

120 VAC NEUTRAL

SEE

APPLICABLE

WIRING

SCHEMATICS

IN THIS

MANUAL

SWITCH BOX