9600 HWG Water Heater

Page 13

Figure 15. Typical installation.

4.

Separate the union on the economizer pipe and

remove the lower half of the union from the

economizer outlet.

5.

Undo the four economizer retainer nuts. (see

Figure 14). Remove the boiler drain valve.

6.

Undo the four clamps that hold the outer shroud

to the upper head. (see Figure 14)

7.

Drop the economizer, inner shroud and outer

shroud together by separating the upper head and

outer shroud.

8.

Clean combustion coil with a wire brush.

9.

Reassembly is done in reverse order. Use

silicone sealer to seal joint between upped head

and outer shroud.

5.6 Combined Water (potable) Heating

and Space Heating

(see Figure 15)
Piping and components connected to this water

heater for the space heating application shall be

suitable for use with potable water.

Toxic chemicals, such as used for boiler

treatment, shall not be introduced into the potable

water used for space heating.

This water heater when used to supply potable

water shall not be connected to any heating system or

component(s) previously used with a nonpotable

water heating appliance.

When the system requires water for heating at

temperatures higher than required for other uses, an

anti-scald mixing or tempering valve shall be installed

to temper the water for those uses in order to reduce

scald hazard potential.

SECTION 6.
Quick Reference Trouble Shooter

6.1 Short Cycling

1.

Tank aquastat set too high

2.

Units shut down before reaching limit.

Continuously restarts without resetting

a.) Limit out of calibration

b.) Wrong air/gas orifices for input or fuel (refer

to 9600 gas orifice chart ONLY)